GE RSTi-EP Functional Safety Manual page 32

Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

Chapter 7. Detailed Descriptions of EP-19xx Modules
Inputs
Safety inputs
Input type
Inputs for start function
Input type
Outputs
Safety output (OSSD)
Output current
Overload protection
Turn-off time
Turn-on time
Auxiliary outputs
Output current
Diagnosis
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
External pre-fusing
Reverse battery protection
Current consumption (I
in the power segment of
IN
the Network Adapter), typ.
Current consumption (IIN in the respective power
segment)
General data
Weight
For additional general data, refer to the section, General Contact Information.
28
2 x 2 channel
Type 3 as per IEC 61131-2
2 (manual start and autostart)
Type 3 as per IEC 61131-2
1
8 A (not for capacitive load)
excess temperature proof and overload-proof, short circuit proof
with external fuse
20 ms
< 2 s
3 x 2
max. 10 A (only to support the inputs dedicated inputs)
Yes
Yes
24 V dc +20%/-15% via system bus
mandatory: super fast, max. 8 A
Yes
8 mA
45 mA
82 g (2.89 oz)
RSTi-EP Functional Safety Manual