Diagnosis
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
External pre-fusing
Reverse battery protection
Current consumption from system current path
I
SYS
Current consumption from input current path I
General data
Weight
For additional general data, refer to the section, General Contact Information.
Byte
0
1
2
3
Standard data format
GFK-2956A
Yes
Yes
20.4V – 28.8V
mandatory: super fast, max. 8 A
Yes
8 mA
45 mA
IN
84 g (2.96 oz)
Process Data
Bit
Description
0
Safety input 0
1
Safety input 1
2
Auto Start
3
Man Start
4
Safety input 0 / channel 1
5
Safety input 0 / channel 2
6
Safety input 1 / channel 1
7
Safety input 1 / channel 2
0
24 V Safe Output
1
SS1 Output
2
24 V DC
3-7
Reserved
Reserved
0-7
0
DIP-Switch Config
1
DIP-Switch Config
DIP-Switch Config
2
DIP-Switch Config
3
4-7
Reserved
November 2017
Chapter 7. Detailed Descriptions of EP-19xx Modules
Status
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - no feed-in, 1 - power feed-in pending
Safety Input 0 - Pulse,1 - No Pulse
Safety Input 0 - Pulse,1 - No Pulse
24 V Safe Outut 00 - No delay, 01 - Delay 1s,
10 - Delay 30s, 11 - Delay 60s
24 V Safe Outut 00 - No delay, 01 - Delay 1s,
10 - Delay 30s, 11 - Delay 60s