Service Facts Single Packaged Cooling/Electric Heat 4TCA4048A1000A N N o o t t e e : : “Graphics in this document are for representation only. Actual model may differ in appearance.” S S A A F F E E T T Y Y W W A A R R N N I I N N G G Only qualified personnel should install and service the equipment.
Pressure Curves Figure 1. 4TCA4048A1 Cooling 1500 CFM INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 67, 63 AND 59 DEG F. OUTDOOR TEMPERATURE (Degree F) INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 67, 63 AND 59 DEG F. OUTDOOR TEMPERATURE (Degree F) COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
Sequence of Operation G G e e n n e e r r a a l l compressor safety controls are closed, the compressor (CPR) will operate with the outdoor fan motor (ODM). Operation of the system cooling (and optional heating) The indoor fan motor (IDM) will operate.
Page 6
Charging in Cooling above 55°F OD Ambient If servicing the equipment requires system evacuation, refrigerant to raise the pressure to match the table, then re-charge the system to the weight specified on or remove refrigerant to lower the pressure. Again, the nameplate.
Troubleshooting Chart P-PRIMARY CAUSES / S-SECONDARY CAUSES SYSTEM FAULTS REFRIGERANT CIRCUIT Liquid Pressure too High Liquid Pressure too Low Suction Pressure too High Suction Pressure too Low Liquid Refrigerant Floodback (TXV System) I.D. Coil Frosting Compressor Runs Inadequate or No Cooling ELECTRICAL Compressor &...
Important Product Information Registering your products helps provide you with one on your invoice or can provide a list for you to use. of the strongest manufacturer limited warranties Please take a few moments to record the following available. To register, go to the manufacturer’s website information to ensure your product registration or contact your dealer.
Page 12
The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org. Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.