Summary of Contents for Ingersoll-Rand 4MUC4518A10N0A
Page 1
Installation, Operation, and Maintenance C-Series Cassette Indoor Units Models: 4MUC4518A10N0A, 4MUC4524A10NA, 4MUC4530A10N0A, 4MUC4536A10N0A, 4MUC4542A10N0A, 4MUC4548A10N0A SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Introduction Read this manual thoroughly before operating or servicing this unit. WARNING Warnings, Cautions, and Notices Proper Field Wiring and Grounding Required! Safety advisories appear throughout this manual as Failure to follow code could result in death or serious required. Your personal safety and the proper operation of injury.
Model Number Description Digit 1: Refrigerant 4 = R-410A Digit 2: Brand name M = Mini-split indoor unit Digit 3: System type U = Universal match heat pump Digit 4: Configuration type C = 4-way cassette Digit 5: Reserved for future use 4 = Standard model Digit 6: Connection type 5 = Flare...
Preparing for Installation Accessories In addition to product literature, the following accessories are supplied with this unit. The type and quantity may differ, depending on the model. Flexible hose Template Insulation A Insulation B Insulation C clamp Flexible hose Cable tie Conduit bracket Note: The required panel is not included with the indoor unit.
9.5 (240) Sub duct connection 10.6 (270) 11.8 (300) Model 4MUC4530A10N0A 4MUC4536A10N0A 4MUC4542A10N0A Dimension/Weight/Diameter 4MUC4518A10N0A 4MUC4524A10N0A 4MUC4548A10N0A 8 (204) 11.3 (288) 10 (253) 13.3 (337) Net dimension 33 x 8 x 33 (840 x 204 x 840) 33 x 11.3 x 33 (840 x 288 x 840) Net weight 34.2 lb (15.5 kg)
Installation Review “Installation Considerations” before proceeding with installation. Follow the procedures in these sections in the order given. Mounting the Unit If the ceiling is already constructed, piping must be laid into position before placing the unit inside the ceiling. CAUTION Avoid equipment damage and personal injury! Ensure that the ceiling is strong enough to support the weight of the indoor unit.
Installation 0.79 in. (20 mm) Indoor unit Ceiling 0.67 in. (17 mm) Gauge Adjust the level of the unit with a leveler. Purging the Unit The unit is shipped from the factory with a holding charge of nitrogen. All of this gas must be purged from the unit.
Installation Installing Refrigerant Piping Connect field-supplied piping using flared connections (not supplied) or by brazing. The large unit port is for gas refrigerant; the small one is for liquid refrigerant. Cut or extend field-supplied piping as needed. Use the following procedures. NOTICE System Failure! If brazing is used for pipe connections, a nitrogen purge is required to prevent the formation of...
Page 11
Installation Conventional flare tool R-410A clutch type Clutch type Wing nut type 0–0.020 in. 0.04–0.06 in. 0.06–0.08 in. 3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is extending above the flaring bar. 4.
Installation Leak Testing Pipe Connections WARNING Confined Space Hazards! Do not work in confined spaces where refrigerant or other hazardous, toxic or flammable gas may be leaking. Refrigerant or other gases could displace available oxygen to breathe, causing possible asphyxiation or other serious health risks. Some gases may be flammable and or explosive.
Installation Installing the Drain System 1. Push the supplied drain hose as far as possible over the drain hose port. • Do not apply excessive force to the piping on the unit side when connecting the drain hose. • Drain hose port locations differ depending on the unit type. Drain connection Drain hose Drain hose port...
Page 14
Installation • Do not install the hose with an upward gradient after the connection port or leaks will result. • The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible. 3.28–4.92 ft (1–1.5 m) •...
Installation Centralized Drainage If the installation requires more than three indoor units, install the main air vent at the front of the indoor unit that is farthest from the main drain. It may be necessary to install individual air vents to prevent water flowing back to each indoor unit. See figure below.
Insulation After determining that there are no leaks in the refrigerant pipes or drainage hose, insulate them as described in these sections. Refrigerant Pipes 1. Use the table below to select the insulation type for each pipe size. Insulation Type Standard conditions High humidity conditions (86°F [30°C], 85%)
Wiring the Unit Observe the following precautions when making electrical connections. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. NOTICE Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors.
Page 18
Wiring the Unit Figure 1. Wiring diagram Outdoor unit Communication cable Circuit breaker Disconnect Indoor unit Grounding Power cable Figure 2. Wiring terminals Indoor unit L1 L2 L1 L2 1(L) 2(N) Cable ties Indoor power Main power cable Communication cable Cable clamp Outdoor unit MS-SVX039A-EN...
Wiring the Unit Electrical Conduit Installation A conduit bracket must be installed to secure the conduit, as illustrated in Figure 3, p. Figure 3. Conduit bracket installation Push Click MS-SVX039A-EN...
Configuration All indoor units are factory configured. If modifications are required, The Technician Utilities Tool (TUT) is strongly recommended. However, any of the following devices can be used: • Technician Utilities Tool (TUT) (instructions follow) • Wireless Remote Control (instructions follow) •...
Configuration Using the Wireless Remote Control To change system configurations using the Wireless Remote Control, follow this procedure: 1. Remove the batteries from the remote control, and re-insert them while pressing the Temp+ and Temp- buttons simultaneously (refer to Figure 4, p. 21).
Configuration The 2-Digit Segments Each 2-digit segment is differentiated from the others by a combination of operation mode and timer on/off icons as shown in Figure Use digit 2 (shown in red in Figure 5) to set the wireless remote to Installation Option #1. Figure 5.
Configuration Installation Option #1 When digit 2 is set to a value of “2, ” the options shown in Table 1 can be set to the values in the right column. Table 1. Installation option #1: Digit 2 = 2 Display screen Digit...
Page 24
Configuration Table 1. Installation option #1: Digit 2 = 2 (continued) Display screen Digit (mode and On/Off) Option description Set digit to... 0: Disabled External control 1: On/Off control 2: Off-only control External control output Thermal on External control output Operation on Not available.
Operation Familiarize yourself with the unit components and operating tips before operating the unit. Components Air flow blade Air intake Air filter (under grill) Display Defrost indicator Filter reset indicator Power indicator (On/Off) Timer indicator Remote control sensor Note: Your unit and display may look slightly different from the illustration shown above, depending on your model.
Operation Internal Protections Internal protections operate if an internal fault occurs in the unit. Type Description Cold air dump The internal fan will be off to prevent a cold air dump when the heat pump is in defrost mode. Defrost cycle The internal fan will be off to prevent a cold air dump when the heat pump is in defrost mode.
Operation Cleaning the Grill and Air Filter 1. Open the blades on the left and right sides of the grill. Press both levers and pull the grill downward. Two safety clips are mounted to the grill to prevent it from dropping. 2.
Operation 4. Clean the grill and air filter with a vacuum or soft brush. If the dust is too thick, rinse them under running water and dry in a well-ventilated area. Note: Drying the air filter in a confined or humid area may cause odors to develop. If odors occur, re-clean and dry it in a well-ventilated area.
Troubleshooting Refer to Table 3 for solutions to common problems and to Table 4, p. 30 for a list of alarm conditions with corresponding error codes and LED behavior. Table 3. Solutions to common problems Problem Solution The unit does not operate The anti-short cycle timer prevents the unit from operating immediately to keep immediately after restarting it.
Troubleshooting If an error occurs, one of more of the LEDs on the display (see “Components” for their location) will flicker. As a protection strategy, the unit stops operating (and the LED turns off). If the unit is turned on before the problem is resolved, the LED will resume flickering and the unit will stop operating again.
Warranty For Trane C-Series Ductless Systems and Related Accessories Warranty For Trane C-Series Ductless Systems and Related Accessories Products Covered This warranty is extended by Trane, and applies to all Trane C-Series Ductless Systems and Accessories for these products which are sold by Trane and applied in accordance with Trane specifications.
Page 32
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.
Need help?
Do you have a question about the 4MUC4518A10N0A and is the answer not in the manual?
Questions and answers