WIKA GDM-100-TA Operating Instructions Manual page 22

Gas density monitor
Table of Contents

Advertisement

Available languages

Available languages

9. Specifications
Accuracy specifications
Start and end of the
measuring range
EN
Stability per year
Switch contacts
Operating conditions
Permissible temperature range
Ambient
Storage
Ingress protection per
IEC/EN 60529
Intended medium
High-voltage test 100 %
Electromagnetic
compatibility (EMC) to
IEC 61000-4
Process connections
Process connection
Electrical connection
Switch contacts
Transmitter
Electrical safety
22
-40 °C: 4 % of span
20 °C: 2 % of span
60 °C: 3.3 % of span
≤ 0.3 % of span
Switching accuracy in the temperature range -20 ... +60 °C
Switch point = calibration pressure P
specification
Switch point ≠ calibration pressure P
chore of the calibration pressure
-20 ... +60 °C (gaseous phase)
-40 ... +60 °C
IP65
pure SF
gas, further gas mixtures on request
6
2 kV, 50 Hz, 1 s (wiring against case)
IEC 61000-4-2 (ESD): Test level 4 (8 kV)
IEC 61000-4-3 (Field): Test level 3 (10 V/m)
IEC 61000-4-4 (Burst): Test level X (±2 kV)
IEC 61000-4-5 (Surge): Test level 2 (±1 kV)
IEC 61000-4-6 (Conducted RFI): Test level 3 (10 V)
G ½ B per EN 837, lower mount
Spanner flats 22 mm
(Option: Flange connection)
other connections and connection locations on request
Cable socket with M20 x 1.5 cable gland
Wire cross-section max. 2.5 mm²
(Option: Plug-in cable box)
With built-in transmitter: Cable outlet
With built-in transmitter: Angular connector (2-pin), IP67 (option:
Field case, stainless steel, IP67)
Protection against reverse polarity and overvoltage
WIKA operating instructions, models GDM-100-TI, GDM-100-TA
: In accordance with customer
E
: Parallel to the reference iso-