5. Commissioning, operation
5.2.1 Limit values for the contact load with resistive load
Maximum rated operating
EN
voltage Ueff
Rated operating current
Switch-on current
Switch-off current
Continuous current
Maximum switching power
Do not exceed the limit values. In order to permanently ensure safe operation, the
following load values are recommended:
Voltage
(per IEC 38)
DC/AC
230 V
110 V
48 V
24 V
The switching current must not be less than 20 mA with low voltages for switching relia-
bility reasons.
Overcurrent protectors
The instruments do not provide for incorporated overcurrent protectors. Should protec-
tors be required, the following values in accordance with EN 60 947-5-1 are to be
recommended.
Voltage 24 V: 2 A
Voltage 250 V: 1 A
14
gas-filled instruments
AC 250 V
1 A
1 A
0.6 A
30 W, 50 VA
gas-filled instruments
resistive load
DC
AC
100 mA
120 mA
200 mA
240 mA
300 mA
450 mA
400 mA
600 mA
For higher loads, and for instruments with liquid-filled cases, WIKA model
905.1X contact protection relays are recommended
WIKA operating instructions, models GDM-100-TI, GDM-100-TA
liquid-filled instruments
inductive
resistive load
load
cos ϕ >0.7
DC
65 mA
65 mA
130 mA
130 mA
200 mA
190 mA
250 mA
250 mA
liquid-filled instruments
AC 250 V
1 A
1 A
0.6 A
20 W, 20 VA
inductive load
AC
cos ϕ >0.7
90 mA
40 mA
180 mA
85 mA
330 mA
130 mA
450 mA
150 mA