Hide thumbs Also See for EML1101:
Table of Contents

Advertisement

Quick Links

Safety Instructions
The user must ensure that all operators are familiar with this operating manual and follow it at all
times.
The operating manual must be read carefully before the instrument is mounted, installed and
commissioned.
All actions taken must follow the operating manual.
Installation and commissioning may only be carried out by appropriately qualified personnel with
due regard for all rules and regulations that are in force.
When the instrument is connected to mains voltage, it must not be opened.
If the instrument is visibly damaged, it must not be installed, wired up or commissioned.
If the instrument does not work after commissioning, it must be
Any further laws, standards, guidelines, etc. relevant to this product must be complied with.
Additional information on EML 1101 Maximum Demand Controller
Loads
which may cause damage or danger when disconnected by EML1101 must
connected to the load channels.
The responsibility for correct load settings, such that proper operation is guaranteed and no
damage or danger arises, remains 100% with the customer.
Important: Read Before Commissioning
disconnected
from the mains.
not be

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EML1101 and is the answer not in the manual?

Questions and answers

Summary of Contents for frako EML1101

  • Page 1 Any further laws, standards, guidelines, etc. relevant to this product must be complied with. Additional information on EML 1101 Maximum Demand Controller • Loads which may cause damage or danger when disconnected by EML1101 must not be connected to the load channels. •...
  • Page 2: Table Of Contents

    Contents PRELIMINARY User Manual EML1101 Contents Section Page Quick Start Programming via Front Fascia....................5 Description FRAKO System options S, M and L..................8 Installation Mounting ..........................8 Electrical Connections ......................8 3.2.1 Power Supply Voltage ......................8 3.2.2 Connecting Inputs.......................9 3.2.3 Connecting Load Channels ....................9 3.2.4...
  • Page 3 User Manual EML1101 Contents Load settings 20 Load name ........................... 20 Priority ..........................20 Power ........................... 21 Preference..........................21 Channel Status........................21 Minimum OFF time....................... 21 Maximum OFF time......................21 Minimum ON time ........................ 22 Group..........................22 8.10 Changing load settings of group channels................22 8.11...
  • Page 4 Quick Start PRELIMINARY User Manual EML1101 19.5 Terminal assignments ......................46 19.6 Connection diagram ......................47 19.7 Dimensions .......................... 48 Appendix 20.1 Glossary of Terms........................ 49 20.2 Preference..........................50 20.2.1 Power preference ......................50 20.2.2 Time preference....................... 50...
  • Page 5: Quick Start

    User Manual EML1101 Quick Start 1 Quick Start The instrument is commissioned as follows: Copy and fill out Form for Basic Settings (page 42 Form for Load Settings (page 45) before commissioning. b) Remove stoppers from the PG cable glands and connect the EML 1101 as shown in Figure 1 on page Please observe the directions in chapter 3 page 8.
  • Page 6 Description PRELIMINARY User Manual EML1101 − Counter constant − Average over (P_act1, Q, P_act2) − Cosphi alarm when cosphi < XX% − Bus address − Auto summer/winter time changeover Note: Settings made are immediately adopted by control system. Please note that when...
  • Page 7: Description

    Usually the average is determined over a period of 10, 15, 30 or 60 minutes. The beginning and the end of a measuring period are sent to the EML1101 by the energy supplier via pulse output on the counter. If a measuring period of 15 minutes is defined, the energy supplier subdivides every day into 24 x 4 = 96 measuring periods.
  • Page 8: Frako System Options S, M And L

    Upgrades to higher system options are carried out with a PC is not necessarily require the assistance of a service technician. For ease of understanding the FRAKO system options are differentiated in the text as follows: Function as of FRAKO system option:...
  • Page 9: Connecting Inputs

    User Manual EML1101 Installation 3.2.2 Connecting Inputs The inputs for active pulse, time pulse and profile switching complies to S0 definition. The power supply required is provided by the inputs. Both potential free contacts and electronic contacts can be connected.
  • Page 10: Installing The Opt-Sw Software

    Commissioning PRELIMINARY User Manual EML1101 EMD error/add-on bus error FRAKO Starkstrombus defect No time pulse No pulse in input 1 (only with activated active pulse control) No pulse in input 2 (only with activated active pulse control) No pulse in input 3 (only with activated active pulse control)
  • Page 11: Commissioning

    Switch on the power supply. The EML 1101 EML1101 MAXIMUM DEMAND CONTROLLER then carries out a self test. The following is Version 2.11 L dependant on program version and the FRAKO system option. d) The standard display is then shown. P_act cosphi P_acc.
  • Page 12: Keyboard

    Operation PRELIMINARY User Manual EML1101 6 Operation Keyboard Cursor buttons − Navigating in menu structure − Changing values and settings − Setting numbers Carriage Return button − Selecting a menu − Moves cursor to next position − Activating stations − Printing MENU button −...
  • Page 13: Menu Structure

    User Manual EML1101 Operation Menu Structure Basic settings Target maximum demand P1, P2, P3 and P4 [ and P4] (section 7.1/7.2) current target maximum demand P1,P2,P3 • Initial value target maximum demand P1, P2, P3, and P4 (section 7.3) •...
  • Page 14: Basic Settings

    Basic Settings PRELIMINARY User Manual EML1101 • Previous day’s power curve (section 9.6) • Power maxima of the last 50 days (section 9.7) • Power maxima of the last 48 months (section 9.8) • Event list (section 9.9) • Delete printer jobs (section 9.10)
  • Page 15: Peak Power P1, P2, P3 And P4

    The absolute limits for actual power P_act is set here for every profile. This function is an extra function provided by EML1101; not to be confused with the control of maximum demand. Depending on the profile activated one of four peak powers is valid.
  • Page 16: Counter Constant

    7.9.8 Bus address This setting assigns an individual address for EML1101 so that the central unit EMIS 1500, the EMG 1500-PN, the communication processor EMP 1100 or the system timer EMT1101 can identify the EML 1101 at the FRAKO Starkstrombus.
  • Page 17: Type Of Profile Switching

    User Manual EML1101 Basic Settings System option Max. number of add-on stations Corresponds with: EML+ EMD 4 + 2 • 8 = 20 Channels 4 + 4 • 8 = 36 Channels 4 + 10 • 8 = 84 Channels The factory default setting is 0.
  • Page 18 Basic Settings PRELIMINARY User Manual EML1101 If the current target maximum demand is exceeded the registered value is adopted as the new target maximum demand. The settings for the self adjusting target maximum demand can be set under this menu item.
  • Page 19: Active Pulse Monitoring Alarm

    If a number of inputs are used (as of FRAKO system option ) a time must be entered that is distinctly higher than the maximum time between two pulses. The input with the lowest pulse rate dictates this value.
  • Page 20: Load Settings

    Load settings PRELIMINARY User Manual EML1101 8 Load settings Programming load settings can be done through the front fascia of EML 1101 or through OPT-SW software (see section 3.3.3 Installation). Program the load characteristics for every load channel used. Programming via the front fascia:...
  • Page 21: Power

    User Manual EML1101 Load settings Always OFF in this profile Power This parameter is used by the EML 1101 to determine whether if a particular load is suitable to be switched back on after switching off. Hereby each OFF load is controlled if the trend would remain under the target maximum demand after switching.
  • Page 22: Minimum On Time

    In the case of power preference, this time can be exceeded in emergency mode. (See 8.4 Preference). Group As of the FRAKO system option it is possible to group channels. This means that the individual channels of a group are switched strictly according to their priority (see section 7.9.10.5 Group).
  • Page 23: Printer Routines

    User Manual EML1101 Printer routines 9 Printer routines Either a PC or a serial printer can be connected to EML 1101 through a built-in RS232 interface. The printer must be configured as follows (EPSON LX300): − Character interval 10cpi − Zero with/without oblique line 0 (not critical) −...
  • Page 24: Error List

    Printer routines PRELIMINARY User Manual EML1101 9.4.1 Error list Press CR button when the display shows "Print Error" when a printout is required. The print out lists the number of errors since last deleted. The following errors are identified: −...
  • Page 25: Power Maxima Of The Last 50 Days

    Target power reset per contact! No message Target power reset per deadline! No message Target power over limit! No message Target power changed via FRAKO bus! No message Target power changed via keyboard! No message Add-on bus error! Add-on bus error ended!
  • Page 26: Deleting Printer Queue

    Add-on stations PRELIMINARY User Manual EML1101 9.10 Deleting printer queue This option allows the cancellation of printing. For example, it may be used to delete unprinted data due to paper jam or other printer errors. 10 Add-on stations In this menu item EMD 1101 Add-on Station can be switched on for the control system and displayed.
  • Page 27: Virtual Add-On Units

    User Manual EML1101 External synchronisation Exception: When the parameter "highest EMD-address" of the EML 1101 is set to 0, the following message is then displayed when you change to ‘Add-on stations’, ‘Display stations’. No display possible due to highest EMD address set to 0 Factory setting for the parameter "highest END-...
  • Page 28: Setting Time

    Setting time PRELIMINARY User Manual EML1101 12 Setting time The date and the time can be set here. Date time setting 29.04.99 14:05:12 Monday Important: If the time or date is incorrectly set, then there are breaks in the data listed.
  • Page 29: Technical Data

    1 add-on interface: For connecting 2/4/10 EMD1101  1 FRAKO Starkstrombus interface For connecting to FRAKO Energy Management System. Operating elements Four membrane buttons Display element Four row illuminated LCD Connections 7x PG cable gland entry to removable...
  • Page 30: Troubleshooting

    Troubleshooting PRELIMINARY User Manual EML1101 17 Troubleshooting 17.1 Checking programmed values 17.2 Control on the instrument First check all the settings entered. The individual measuring points, as with the settings, are to be checked thoroughly and their values shown on the display and compared with their entries.
  • Page 31: Sources Of Error

    9600. Incorrect command order during the configuration Are the FRAKO Starkstrombus  and the Add-on bus Individual bus faults connected ? (Contacts 1-3 and 4-6) Solution: Disconnect buses. There should be no connection between the two.
  • Page 32 Troubleshooting PRELIMINARY User Manual EML1101 Error Possible causes...
  • Page 33: Application Instructions

    PN is grounded, then the shielding at EML 1101 is not to be grounded. Do not connect the shielding to the metal cable gland, it should only be connected to the GND terminal If this is not done, then errors can occur in FRAKO Starkstrombus and result in EML 1101 not being recognised on the bus.
  • Page 34: Operating Opt-Sw Via Modem

    Application instructions PRELIMINARY User Manual EML1101 18.4 Operating OPT-SW via modem The EML modem is configured via a terminal program. Important: Be sure that the baud rate of the terminal program is set to 9600 baud! The baud rate set in the terminal program is adopted by the modem. If the wrong baud rate is set, no connection can be made.
  • Page 35 User Manual EML1101 Annex Term Meaning Correction power P_corr − ⋅ corr trend − Control detects the necessary switching on the basis of the correction power. Negative value means switching off. Emergency load shedder channel This channel is switched off last.
  • Page 36: Annex

    All of the items described above can cause a loss of programming in unfavourable conditions so that the instrument can only be put in order by FRAKO service personnel. For this reason please take great care and follow the instructions exactly.
  • Page 37 User Manual EML1101 Annex OPTSW: Authorisation of an instrument update Authorisation code Run update After the authorisation code has been entered the following warning appears: Attention Please read the following instructions completely! If the instructions are not followed correctly, the instrument may require service.
  • Page 38 PRELIMINARY User Manual EML1101 Important! Disconnect the instrument from the FRAKO Starkstrombus by pulling the left connection (contact 1-3) in the contact compartment. If this is not disconnected the update will be interrupted after the transfer of the boot loader. If this should have happened follow the following instructions: Disconnect the EML from the mains for ca.
  • Page 39 The EML is now ready! Click OK to conclude the update! Program update error. Check if the FRAKO bus is disconnected and that the instrument is switched on. Should one of these be the case remedy it and restart the update. Upgrade to An upgrade to a higher FRAKO system option can only be carried out with EML software version 1.70...
  • Page 40: Table Of Settings

    Only affects display. P_act2, Q) Cosphi Alarm at Limiting value for cosphi alarm. 0.00 - 0.99 Cosphi < XX % Bus Address Address of EML at FRAKO 9-125 Starkstrombus Auto Activates / deactivates automatic setting of Yes/ No winter/summer summer and winter time...
  • Page 41 User Manual EML1101 Annex Pos. Designation Description Units Value range Options Number of profiles Limits profile dependant entries in the used. basic and load settings. Highest add-on Limits the add-on stations to the set value. 0-2, M 0-4, L 0-10...
  • Page 42: Form For Basic Settings

    Annex PRELIMINARY User Manual EML1101 19.3 Form for Basic Settings Customer: _________________________________ Date: ________________ Plant: _________________________________ Station: ________________ ________________ Remarks: _________________________ Target maximum demand P1 (Self Target maximum demand for profile 1 adjusting target maximum demand inactive) Current Target maximum demand for Profile 1...
  • Page 43 User Manual EML1101 Annex Counter and transformer data Counter constant(P_act1) Imp/kWh Printed on counter Imp/Wh Voltage transformer (P_act1) Ratio Up/Us Printed on U-transformer Current transformer (P_act1) Ratio Ip/Is Printed on I-transformer Average over (P_act1) Number of Standard settings = 1...
  • Page 44 Annex PRELIMINARY User Manual EML1101 active Self adjusting target inactive maximum demand over external signal positive negative both over internal date Day: Hour: Minute: Active pulse monitoring Allow grouping Units Determines units of power entries.
  • Page 45: Form For Load Settings

    User Manual EML1101 Annex 19.4 Form for load settings...
  • Page 46: Terminal Assignments

    Annex PRELIMINARY User Manual EML1101 19.5 Terminal assignments Terminal No. Description Notes FRAKO Starkstrombus channel A FRAKO Starkstrombus channel B FRAKO Starkstrombus GND Add-on bus channel A Add-on bus channel B Can be connected to ground via jumper Add-on bus GND...
  • Page 47: Connection Diagram

    User Manual EML1101 Annex 19.6 Connection diagram Important: When working on EML 1101, ensure that the unit is disconnected from mains. Although the EML 1101 is disconnected from mains, the circuits leading to switch contacts may still be connected to power voltage.
  • Page 48: Dimensions

    Annex PRELIMINARY User Manual EML1101 19.7 Dimensions All Dimensions are in millimeter Units. Figure 2: Enclosure Up cursor button Down cursor button CR button MENU button Figure 3: Buttons...
  • Page 49: Appendix

    User Manual EML1101 Annex 20 Appendix 20.1 Glossary of Terms Maximum demand – The maximum amount of power drawn, measured in kW, during a measuring period. Measuring period – The time period which EML 1101 limits maximum demand to target maximum demand for different profiles.
  • Page 50: Preference

    If the time settings are more important than the maximum demand, set this load to time preference. In this case the time settings are sure in any working condition of EML1101. For example in the emergency mode this load would be switched on, even if there is an exceeding power demand. If the...

Table of Contents