Disabling PV Link

IMPORTANT NOTE: Disabling a PV Link does NOT de-
energize the PV array if SnapRS devices are not
installed. If SnapRS devices are installed, in-array volt-
ages are limited to less than 80 VDC.
IMPORTANT NOTE: Disabling PV Link does not de-
energize the DC bus if other devices are providing power
to the DC bus.
IMPORTANT NOTE: The disabled/enabled state of
each PV Link persists through AC power outages and DC
bus power cycling.
To disable a PV Link:
1. On the Generac PWRcell Inverter control panel,
use the left or right arrows to scroll to the page for
the desired PV Link.
2. Press the center button to enter device settings.
3. Use the up and down arrows to highlight Disable
and press the center button to select.
4. Arrow right and press the center button to Confirm.
5. Repeat steps 1–4 to disable any additional
optimizers in the system.
NOTE: Repeat the process to re-enable each optimizer.

AFD Self-Test

NOTE: Arc fault detection is always enabled.
Performing an arc fault detection (AFD) self-test confirms
arc fault functionality is working properly. When an arc
fault is detected, the status message reads Arc Fault.
To conduct an AFD test:
1. On the Generac PWRcell Inverter control panel,
use the left or right arrows to scroll to the page for
the desired PV Link.
2. Press the center button to enter device settings.
3. Use the up and down arrows to highlight Test AFD
and press the center button to enter the test state.
4. Arrow right and press the center button to Confirm
Upon test completion, the control panel will display a
result of Test Success or Test Failure. After a few
seconds, the AFD test will automatically clear.
Installation Manual for PV Link

PVRSS Self-Test

After commissioning, you can verify proper function and
configuration of the PVRSS system at any time by
manually running the PV Link PVRSS self-test.
To run the PVRSS self-test:
1. On the Generac PWRcell Inverter control panel
press the right arrow button repeatedly until the
first PV Link device page appears.
NOTE: The device page display should read Disabled. If
it does read not Disabled, press the center button and
Disable the PV Link.
2. Press the center button and select Test PVRSS. to
enter the Testing PVRSS state.
The display indicates Testing PVRSS during the test
process, which can take up to three minutes. Upon
successful completion, the display will read: Test
Success.