Switches 11 and 12 −− Heating Mode Blower Speed −−
Switches 11 and 12 are used to select heating mode blower
motor speed. The unit is shipped from the factory with the
dip switches positioned for medium low (2) speed indoor
blower motor operation during the heating mode. The table
below provides the heating mode blower speeds that will
result from different switch settings. Refer to blower data
tables at the front of this manual for corresponding cfm val-
ues.
TABLE 26
Heating Mode Blower Speeds
Speed
1 − Low
2 − Medium Low
(Factory)
3 − Medium High
4 − High
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and
R on the integrated control board, must be cut when the fur-
nace is installed with either the Harmony II zone control
board or the CCB1 EfficiencyPlus humidity control. Refer to
table 27 for operation sequence in applications including a
G32V, CCB1 and single−speed outdoor unit. Table 28 gives
the operation sequence in applications with a two−speed
outdoor unit.
OPERATING MODE
System Condition
Normal operation
*Call for humidity
removal during
cooling demand
Dehumidification
demand satisfied
during cooling demand.
Call for cooling after
call for humidity
call for humidity
removal.
Humidity demand
satisfied between
satisfied between
thermostat demands
(unit off cycle).
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther-
mostat heating demand.
* Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
Switch 11
Switch 12
On
On
Off
On
On
Off
Off
Off
G32V−5, CCB1 and Single−Speed Outdoor Unit
SYSTEM DEMAND
Thermostat
*Relative Humidity
Demand
(EfficiencyPlus Lights)
No demand. Humidity
Y1
level is acceptable
Humidity level rises
Y1
above setpoint. Demand
Humidity level falls below
Y1
setpoint. No demand
Humidity level above set-
None
point. Demand initiated.
Humidity level above set-
Y1
point. Demand initiated.
None
Over setpoint (1 or more)
Y1
Change to acceptable
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O
on the integrated control board, must be cut when the fur-
nace is installed in applications which include a heat pump
unit and the FM21 FuelMaster control board.
On−Board Jumper W915
On board jumper W915, which connects Y1 to Y2 terminals
on the integrated control board terminal strip must be cut if
two−stage cooling will be used.
On−Board Jumper W6
On board jumper W6 is an external measuring device for in-
door blower CFM. If by chance W6 is cut, the CFM LED will
not operate but the furnace will operate as normal. The
jumper has no affect on furnace operation.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, variable
speed integrated control just to the left of the first bank of dip
switches. These lights' flashes correspond with diagnostic
codes detailed on in table 21.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate
operating status. The green ON/OFF LED is lit any time the
blower is operating. The green CFM LED indicates the
blower motor speed. Count the number of blinks between
the two−second pauses to determine the CFM. Each blink
represents approximately 100 CFM. The yellow HI/LO LED
is lit when the W914 (DS to R) jumper has not been clipped
for CCB1 or Harmony operation. The yellow HEAT LED is lit
when the indoor blower is operating at the HEATING
speed.
TABLE 27
Blower
CFM
(COOL)
COOL
77%/74%
of COOL
initiated.
COOL
Off
77%/74%
of COOL
Off
COOL
Page 28
SYSTEM RESPONSE
Comments
Compressor demand and indoor blower
speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1
control. Indoor blower speed reduced by
CCB1 control.
When humidity demand is satisfied, blow-
er speed immediately increases to the
COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when rela-
Dehumidification mode begins when rela
tive humidity is greater than setpoint.
While unit is not operating (no thermostat
demand), slide switch is moved down and
demand) slide switch is moved down and
back up. Blower operates at COOL CFM.