Uim 02A - Huawei TP48200A-D17B3 Troubleshooting Manual

Table of Contents

Advertisement

TP48200A-D17B3
Troubleshooting Guide
Table 2-3 Button description
Button
▲ or ▼
Cancel
Enter
NOTE

2.5 UIM 02A

The UIM 02A panel provides sensor detection ports, Boolean value input ports, dry contact
outputs, and communications ports.
Figure 2-6 UIM 02A panel
Table 2-4 Port description
Port Type
Sensor port
Analog value
detection
Issue 03 (2013-05-06)
Description
Allows you to view menu items and set the value of a menu item.
Returns to the previous menu without saving the settings of the current
menu item.
Enters the main menu from the standby screen, enters a submenu from the
main menu, or saves the settings of a submenu item.
After a menu is displayed, the standby screen is displayed if no button is pressed within 5 minutes.
After a menu is displayed, the LCD screen becomes dark if no button is pressed within 8 minutes.
On the standby screen, the LCD contrast can be decreased by pressing ▲ and Enter simultaneously or
be increased by pressing ▼ and Enter simultaneously.
Silkscreen
TEM_BAT
GATE
SMOKE
WATER
TEMHUM
AIN
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
2 TP48200A-D17B3 Overview
Description
Used by the battery temperature sensor.
Used by the door status sensor.
Used by the smoke detector.
Used by the water detector.
Used for detecting the battery status.
Used by the battery temperature sensor.
13