Item
Description
CO
sensor low range 0...Min. of high range
CO2L
2
VOC sensor high
UOCH
range
VOC sensor low
UOCL
range
HUMH Humidity sensor high
range
Humidity sensor low
HUML
range
Temperature sensor
TEMH
high range
Temperature sensor
TEML
low range
PM2.5 setpoint high
SPMH
range
PM2.5 setpoint low
SPML
range
CO
setpoint high
SPCH
2
range
CO
setpoint low
SPCL
2
range
Fan type selection
FAN
ECM fan output limit
ECMH
high
ECM fan output limit
ECML
low
Filter time display
TC
A6V11439451_----_c
Range
Max. of low range...100
0...Min. of high range
Max. of low range...100
0...Min. of high range
Max. of low range...100
-50...Min. of high range
Max. of low range...500
0...Min. of high range
Max. of low range...2000
0...Min. of high range
1: 1 speed fan (ON/OFF)
3: 3 speed fan
4: 4 speed fan
5: ECM fan
Max. of ECML...100 %
0...Min. of ECMH
0: Disable
Factory settings
0
5
0
100
0
50
0
100
12
1500
500
3: 3 speed fan
80 %
30 %
0: Disable