Download Print this page

Honeywell Ex-Or MLS Installation And Commissioning Instructions page 4

Hi-bay detector, dsi/dali ballasts

Advertisement

Dimensions
62mm
deep
100mm
Technical Data
2
MLS CABLE: 1.5mm unscreened twisted-pair : see Application Note AN4001
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 16.0m
o
RANGE: 360 cone-shaped detection pattern, diameter (at floor level) = 1 x mounting height
MINIMUM MOUNTING PITCH (SPACING): 0.5 x mounting height (regulating mode only)
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps
CAPACITY: 25 ballasts
OUTPUT: 2-wire digital polarity free
PHOTOCELL: Regulating
OFF DELAY: Adjustable via Programmer - factory pre-set to 20 minutes
DEPTH REQUIRED BEHIND CEILING (FLUSH VERSION): 62mm from front flange plus an
allowance for the minimum bend radius of the cables.
WEIGHT: 200g approx
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: 4X
OPERATING TEMPERATURE: 0 C to 40 C
Ex-Or
Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
Flange: 10mm deep
h
d
o
o
Electrical Connections
OneSwitch
L
N
BALLAST
CONTROL
230V 50Hz
Mains Supply
Polarity-free Digital Output
to compatible luminaires
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
MLS Bus
Connection
To further
MLS Devices
W4451F