Technical Data - Busch-Jaeger Busch-easycare 1518 USV Manual

Table of Contents

Advertisement

Available languages

Available languages

®
Busch-easycare
9

Technical data

Input
Nominal voltage
Nominal voltage range
Input frequency
Output
Nominal current
Output voltage in mains operation
Output voltage in battery operation
Rated output power
Ripple for nominal output current
Battery capacity
Charging current
Bridging time for nominal current
Battery voltage thresholds
Switching threshold for UPS operation
Switching threshold for warning prior to
battery switch-off
Switching threshold for total discharge protection
EMC CE-certified
Safety
Output
Testing voltage PRI – SEC
Protection class
Degree of protection
General
Permissible ambient temperature in operation
Permissible ambient temperature
during storage and transport
MTBF
Technical manual 0073-1-8701
115 - 230 V AC
90 - 264 V AC
47 - 63 Hz
6 A DC
24 V DC +/- 2%
Typ. 26.5 - 20 V DC
144 W
< 20 mVeff
7 Ah
Typ. 600 mA, temperature-dependent
Approx. 36 min.
Ue < 92 V AC
Typ. 22 V
Typ. 20 V
EN 55022; EN 61000-3-2, -3;
EN 61000-4-2, -3, -4, -5, -6, -11
EN 60950-1
Safety Extra Low Voltage (SELV)
2 kV
Class I
IP 20
0 - +40°C
-25 - +40°C (for optimum battery life:
cool and dry)
200,000 h at 25°C (without batteries)