GENERAL
The Honeywell XIO-10HUB Extension Module provides
additional potential free contacts as supporting contacts to
connect digital outputs, analog outputs, etc. Six contacts each
are interconnected. A maximum of 60 volts can be applied to
the contacts. The extension module can be used as a power-
on module for bus connection, supply voltage and potential
distribution.
SPECIFICATIONS
Electrical Ratings:
Supply Operating Voltage: 10 to 28 V AC/DC.
LED Current Consumption: 0 mA (AC) / 0 mA (DC).
Load:
Nominal Current:
Bus: 2.5 A max.
Contacts: 8.0 A max.
Prefusing:
Bus: 3.0 A max.
Contacts: 10.0 A max.
Terminal Blocks:
Supply and Bus: 16 AWG (1.5 mm
(Terminal block and strapping plug included in packing).
2
2
) or 14 AWG (2.5 mm
)
INSTALLATION INSTRUCTIONS
Temperature Ratings:
Operating: 23° F to 131° F (-5° C to +55° C).
Storage: -4° F to +158° F (-20° C to +70° C).
Dimensions (W x H x D):
1.4 x 2.7 x 2.8 in. (35 x 70 x 71 mm).
Weight: 2.6 ounces (75 g).
Mounting Position: Any.
Construction Material:
Housing and Terminal Blocks: Polyamide 6.6 V0.
Faceplate: Polycarbonate.
Protection:
IP40 housing DIN 40050.
IP20 terminal blocks DIN 40050.
Approvals:
UL 916, Standard for Energy Management Equipment.
European Community Mark (CE) Listed.
SAFETY INSTRUCTIONS
NOTES REGARDING DEVICE DESCRIPTION
These instructions include indications for use and mounting of
the device. In case of questions that cannot be answered with
these instructions, please consult the product supplier or
manufacturer. It is the responsibility of the equipment installer
to ensure that all federal, state and local codes are followed.
SAFETY INSTRUCTIONS
• Keep these Installation Instructions for industrial safety and
the prevention of accidents.
• Only qualified personnel shall do mounting and installation
work with these devices, see section titled "Qualified
Personnel".
• The information in these instructions must be read and
understood by every person using this device.
QUALIFIED PERSONNEL
Qualified personnel in the sense of these instructions are
persons who are well versed in the use and installation of
such devices and whose professional qualification meets the
requirements of their work.
95-7717—2

Advertisement

loading

Summary of Contents for Honeywell XIO-10HUB

  • Page 1 UL 916, Standard for Energy Management Equipment. European Community Mark (CE) Listed. GENERAL SAFETY INSTRUCTIONS The Honeywell XIO-10HUB Extension Module provides additional potential free contacts as supporting contacts to NOTES REGARDING DEVICE DESCRIPTION connect digital outputs, analog outputs, etc. Six contacts each are interconnected.
  • Page 2 (3) Wire diameter minimum 28 AWG (0.3 mm) up to 16 AWG (1.4 mm). Mount the XIO-10HUB Extension Module on standard DIN rail per DIN EN 50022 (1.35 x 0.3 in. [35 x 7.5 mm]), in junction 4. Prepare cable for module connections.
  • Page 3 COMPACT I/O MODULE TERMINATION Fig. 1 shows the termination points of the XIO-10HUB. E2 E1 GND +24V 10 A E1 GND +24V 10 A +24 V +24 V E2 E1 GND +24V E1 GND +24V Bus-Stecker max. 3 A XIO-10HUB M25039 Fig.
  • Page 4 COMPACT I/O MODULE By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...