Conditions for Certification:
i.
The IP64 was followed IEC/EN 60079-0, the IP66/67 as per IEC/EN 60529.
ii.
The equipment shall not be installed in a location where the external conditions are conducive to the build-up of electrostatic
charge on such surfaces. In addition, the equipment shall only be cleaned with a damp cloth.
iii.
All cable entry holes shall be fitted with either an IECEx / ATEX certified cable gland or an IECEx / ATEX certified stopping plug
that is suitable for the application. The type of cable, glands and stopping plugs shall have temperature ratings of at least 70°C.
iv.
The terminals shall only be fitted with wires that have cross sectional area falling within the following limitations:
WAGO 2004-conductor series terminals: single-core, finely stranded and standard: min. 0.5 mm
WAGO 862-conductor series terminals: single-core, finely stranded and standard: min. 0.5 mm
Weidmüller Type MK6 series terminals: single-core, finely stranded and standard: 0.5 mm
DECA: BCM121 conductor series terminals: single-core, finely stranded and standard. 0.5 mm
v.
All fixing screws for sealing on enclosure will be torqued to 5.5±0.5Nm.
vi.
The equipment shall be installed such that the supply cable is protected from mechanical damage. The cable shall not be
subjected to tension or torque. If the cable is to be terminated within an explosive atmosphere then the free end shall be
terminated in a suitably certified termination facility.
vii.
The installation shall provide a controlled environment that limits the pollution degree to the pollution degree 2 or better as
defined in EN 60664-1.
viii.
Temperature code depends on ambient temperature as follows:
Note: P2***********F, P2***********G, P4***********F or P4***********G luminaire can be used in ambient temperature "-20°C to 50°C" only.
SafeSite® GRP LED Linear for ATEX/IECEx
T-code
Ambient
Temperature
T5 and T95°C
-20°C to 50°C
T4 and T130°C
-40°C to 65°C
2
to 6 mm
to 4 mm
2
to 6 mm
2
2
to 4 mm
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
732 919 3119
Tel:
Fax: 732 751 5778 www.dialight.com
2
2
2
2
9100-127-3882-99 REV A