Dialight SafeSite Operating Instructions Manual page 3

Grp led linear for atex/iecex
Hide thumbs Also See for SafeSite:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Technical Data:
Category of Application:
Ex tb op is IIIC T130°C Db
P*(B/T)***********
IECEx SIR 19.0069X
Sira 19ATEX9228X
Ex ec IIC T4 Gc
Ex tc IIIC T130°C Dc
P*(B/T)***********
IECEx SIR 19.0069X
Sira 19ATEX4227X
Rated Input
Voltage:
100-277 VAC 50/60 Hz
P***********N
120-250VDC
P***********(F/G)
230/240 VAC 50 Hz
Rated Input Current:
0.1A at 230V AC
P2************
0.2A at 110V AC
0.2A at 230V AC
P4************
0.5A at 110V AC
Inrush Current @230VAC:
P2************
15A (0.5ms)
P4************
15A (0.5ms)
Operating
-40°C to +65°C
Temp.
Emergency
-20°C to +50°C
Models
Housing:
Glass Reinforced Polyester
Dimensions:
See diagram page
Standard: M25 x 1.5mm
Cable Entries:
Reducer: M20 x 1.5mm
IP 66/67 as per
Locations:
IEC 60529
Terminal block:
3 Phase
7 way
Conductor
See diagram page
Size:
Strip Length:
See diagram page
Through cable:
3 Phase
7 x 2.0 mm²
Tightening
See Technical Diagrams
Torques:
Weight:
P2**********N
7.9 kg[17.4 lbs.]
P2**********(F/G)
8.7 kg[19.2 lbs.]
P4**********N
10.9 kg[24.0 lbs.]
P4**********(F/G)
11.9 kg[26.2 lbs.]
SafeSite® GRP LED Linear for ATEX/IECEx
Safety Instruction:
The installation, operation and
maintenance must be carried out by an
electrician suitably trained in hazardous
areas with knowledge of increased safety
explosion protection IEC 60079-14.
The technical data indicated on the
LED luminaires are to be observed.
Changes of the design or
modifications to the LED luminaire are
not permitted
Observe the national electrical safety
rules and regulations during
installation.
No user serviceable parts inside.
Conformity with Standards
This equipment conforms to the standards
specified in the Declaration of Conformity. It
has been designed, manufactured and
tested in accordance with BS EN 9001.
ATEX Directive 2014/34/EU: Equipment and
protective systems intended for use in
potentially explosive atmospheres.
EMC Directive 2014/30/EU: Electromagnetic
compatibility.
Equipment Application
This lighting equipment is intended for use in
a
potentially
explosive
hazardous locations to the requirements of
ATEX Directive 2014/34/EU. See product label
for zone.
This product can be used indoors or outdoors
to
illuminate
areas
explosive atmosphere.
Mounting the Luminaire
Assemble the mounting bracket to the
luminaire with two M8 x 1.25 by 16 mm bolts.
Torque specification: 5.5 N-m [47.7 in.-lbs.]
maximum.
Installation
Ensure that the mains voltage supply is
disconnected
before
luminaire.
Install
the
accordance
with
the
instructions as well as any other applicable
electric codes.
Always transport and store the equipment in
its original packaging and keep in a dry
location. When unpacking check for any
cracks or damage in the housing or lens. If in
doubt, do not install.
NOTE: The cabling used must be suitable for
the
site
application
requirements.
When assembling the cable entries for the
mains
manufacturer's specifications for the glands
used. Unused cable entries must be closed
and sealed by a certified blanking plug.
NOTE: This luminaire is supplied with a single
dust cap to be replaced by a suitable cable
gland. The other entries are supplied with IP-
66/67 blanking plugs.
The cable entry should be rated to a
minimum of IP66/67 as per IEC 60529 to
maintain
luminaire. The cable entries should be
securely tightened
minimum protection rating is achieved. A
locknut is required for each cable gland to
ensure they are securely fastened in place.
WARNING: Do not over tighten as the
protection rating may be compromised.
Always refer to the gland manufacturer's
data for torque settings.
Cable gland with O-ring to have minimum
thread length of 10mm.
Opening the End Caps
To open the end cap, unscrew the four
screws at either end of the unit. Once these
screws are loosened sufficiently the end cap
atmosphere
in
will come off the fixture.
The terminal blocks are mounted to the
terminal mounting plates at each end of the
unit.
with
a
potentially
When replacing the end covers, ensure the
seals are clean and undamaged. Do not
allow any cables, wires, or retention elements
to be trapped by the end covers. Ensure that
all wires are clear from the screw entry points.
Electrical Connections
This
luminaire
through wire capabilities and as such, the
mains can enter the luminaire from either
end.
connecting
the
The terminal block is suitable for multi-
equipment
in
stranded or single core wires. The parameters
manufacturer's
can be found in Technical Data.
When
insulation of the conductors shall reach up to
the terminal block. The conductor itself shall
not be damaged. The connectable minimum
and maximum conductor cross sections shall
be observed (see Technical Data box).
See technical diagram area for terminal
block usage instructions
and/or
the
site
WARNING: Only single wires to be used on
each terminal entry point.
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
732 919 3119
Tel:
Fax: 732 751 5778 www.dialight.com