Factory Settings - Vents PU JK 01 User Manual

Lcd control panel
Table of Contents

Advertisement

Parameter
Parameter
Code
6
Duct Temperature
7
Room Temperature
11
Timer Operation - Temperature
12
Timer Operation - Air Flow.
Air Flow at Low Speed in Air
18
Supply Mode
Air Flow at Medium Speed in
19
Air Supply Mode
Air Flow at High Speed in Air
20
Supply Mode
21
Temperature Sensor Selection.
22
Standby Mode Air Flow
23
Standby Mode Temperature
Air Flow at Low Speed in Air
29
Extract Mode
Air Flow at Medium Speed in
30
Air Extract Mode
Air Flow at High Speed in Air
31
Extract Mode
33
Supply Fan Shutdown.
34
Supply Fan Operation Time
35
Supply Fan Idling Time
Supply Fan Shutdown
36
Temperature
39
Bypass Operation Mode.
41
Duct Humidity
Measurement
Measurement
Units
Range
°С
10-30
°С
10-30
°С
10-40
-
1, 2, 3
%
0-99
%
0-99
%
0-99
-
0.1
-
0.1
°С
10-30
%
0-99
%
0-99
%
0-99
-
1.0
min.
5-60
min,
5-60
°С
-5 ... +5
-
1.0
%
10-80
RECYCLE AT THE END OF THE SERVICE LIFE.
DO NOT DISPOSE THE PRODUCT WITH UNSORTED MUNICIPAL TRASH.

FACTORY SETTINGS

Purpose
Temperature in the air duct.
Room temperature.
Room temperature for timer operation.
Ventilation mode for timer operation.
Air fl ow in the supply air duct at low speed (defi ned as a
percentage of the maximum unit capacity).
Air fl ow in the supply air duct at medium speed (defi ned
as a percentage of the maximum unit capacity).
Air fl ow in the supply air duct at high speed (defi ned as
a percentage of the maximum unit capacity).
Selection of the Active Temperature Sensor:
0 — Duct;
1 — Room.
Air Flow Rate in the Standby Mode.
User-defi ned Temperature in the Standby Mode.
Air fl ow in the exhaust air duct at low speed (defi ned as
a percentage of the maximum unit capacity).
Air fl ow in the exhaust air duct at medium speed
(defi ned as a percentage of the maximum unit capacity).
Air fl ow in the exhaust air duct at high speed (defi ned as
a percentage of the maximum unit capacity).
Selection of the freezing protection logic by shutting
down the supply fan:
1 — ON;
0 — OFF.
Supply fan operation time while the supply fan
shutdown mode is enabled.
Supply fan idling time while the supply fan shutdown
mode is enabled.
The air duct temperature set point to enable freezing
protection activation logic by shutting down the supply
fan.
Bypass operation mode selection:
0 — Regular operation mode to prevent heat exchanger
freezing at low temperatures;
1 — Bypass opening for the ventilation mode.
Humidity level in the air duct.
9
Default
Value
25
20
20
1
40
70
99
0
1
20
40
70
99
0
20
5
+3
1
50