Danfoss AK-PI 100 Instructions page 2

Woodley protocol interface

Advertisement

Supply voltage:
Transformer
Class II
The 24 V must not be
shared by other
controllers or units
The 24 V input must not
have earth connection
Quick setup
1. Address = 000 (Factory setting)
2. Connect service tool
3. Configuration (IP and MDM/WTP). See manual.
4. Disconnect service tool
5. Set address on AK-PI 100
e.g. 012 ( from 11 to 199)
2
Instructions RI8MK102 © Danfoss 3/2008
6. Connect to Woodley 4 way TPI card. (WTP) or to
Woodley MDM-PI (MDM)
7. Connect to AK-SC 255
8. AK-SC 255 configuration
a) Ethernet
b) I/O Network
c) Rescan
d) PI 100/ 200
e) Mark PI-address
f ) Rescan
g) Configuration /Refrigeration / Add controls / Setup
Further information !
AK-PI 100 manual / AK-SC 255 manual