Option
SEG13
Explanation
Indication Details
Indication
and Details
2
Option
SEG19
Explanation
PAGE
Indication Details
Indication
and Details
3
(*1)
Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at
the lowest place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at
the lowest place, select the option "1".
(*2)
Distance : The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and
the pipe length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is
40 m(131.23 ft) away from an outdoor unit, select the option "2".
(100 m(328 ft) - 40 m(131.23 ft) = 60 m(196.85 ft))
(*3)
For MTFC option, MTFC(Multi Tenant Function Controller) kit is required.
(*4)
Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to
using external heater
e.g. 1)
Setting 02 series SEG9 ="1" / Setting 05 series SEG18 = "0": Hot water heater is turned on at the same time as the
heating thermostat is on, and turned off when the heating thermostat is off.
e.g. 2)
Setting 02 series SEG15 ="2" / Setting 05 series SEG18 ="A":
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 4.5 °C(8.1 °F) for 10 minutes.
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 4.5 °C(8.1 °F) + 1 °C(1.8 °F) [1 °C(1.8 °F) is
the Hysteresis for On/Off selection.
SEG14 SEG15 SEG16
SEG17
SEG20 SEG21 SEG22
Indication
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Control variables when using hot water / external heater (*4)
Indication
Set temp. for heater On/Off
0
At the same time as thermo on
1
At the same time as thermo on
2
At the same time as thermo on
3
4
5
6
7
8
9
A
B
C
D
E
SEG23
Forcing FAN Operation for Heating and Cooling
Details
Cooling Fan Setting
Heating Fan Setting
Disuse
Disuse
Use (Fan: User setting)
Disuse
Use (Fan: High)
Disuse
Use (Fan: Low)
Use (Fan: User setting)
Use (Fan: User setting)
Use (Fan: User setting)
Use (Fan: User setting)
Use (Fan: High)
Use (Fan: User setting)
Use (Fan: Low)
Use (Fan: High)
Use (Fan: High)
Use (Fan: User setting)
Use (Fan: High)
Use (Fan: High)
Use (Fan: High)
Use (Fan: Low)
Use (Fan: Low)
Use (Fan: Low)
Use (Fan: User setting)
Use (Fan: Low)
Use (Fan: High)
Use (Fan: Low)
Use (Fan: Low)
SEG18
Details
Delay time for heater On
No delay
10 minutes
20 minutes
1.5 °C
No delay
1.5 °C
10 minutes
1.5 °C
20 minutes
3.0 °C
No delay
3.0 °C
10 minutes
3.0 °C
20 minutes
4.5 °C
No delay
4.5 °C
10 minutes
4.5 °C
20 minutes
6.0 °C
No delay
6.0 °C
10 minutes
6.0 °C
20 minutes
SEG24
Disuse
Disuse
Disuse
Disuse
33