Generac Power Systems 50 Hertz Air-cooled Generators Installation Manuallines page 10

Table of Contents

Advertisement

Available languages

Available languages

General Information
4. The circuit breaker is attached to the exterior access panel.
5. Remove the plastic plugs inside the main breaker access area
to allow connection of the power leads to the circuit breaker.
6. Now connect the power leads to the circuit breaker. Since this
is a single-phase application, it doesn't matter which power
lead is connected to which lug.
7. Connect the green equipment ground wire to the ground bus
bar and torque to 35 inch lbs. The torque values are:
• 10-14 AWG = 35 in/lbs
• 8 AWG = 40 in/lbs
• 4-6 AWG = 45 in/lbs
8
8. Connect the control wires to the correct terminals. The
terminals are clearly marked N1 and N2 for utility sensing; 23
and 194 for transfer relay control; and T1 and T2.
In order to maintain separation of circuits, the DC control wires
must be separated from the AC control wires. A piece of fiber-
glass sleeving has been provided in the manual kit to achieve
this. Slide the sleeving over the AC wires OR the DC wires, but
not both, from the wire landing area to the outside of the gen-
erator. Use the cable tie locations to hold the sleeving in place.
An improperly connected control wire can damage the generator
control board.
T2
Ground
Cable Tie
Location
NOTE:
NOTE: