The programme of HVI Conductor system components consists of a HVI
product range of connecting and fixing elements for this conductor.
The design and installation of HVI
1.

Installation and use

The HVI
®
Conductor is a high-voltage-resistant, insulated down conductor with a voltage-controlled
outer sheath.
It is typically used as insulated down conductor in lightning protection systems to maintain the separation
distance in accordance with IEC 62305 Part 3 (DIN EN 62305-3) (VDE 0185-305-3). At first, the separation
distance has to be calculated as explained in IEC 62305 Part 3 (DIN EN 62305-3 (VDE 0185-305-3),
Subclause 6.3, with a material factor of k m = 1 in air, or k m = 0.5 for solid material. It has to be tested
if this calculated separation distance can be realised with the equivalent separation distance of the
®
HVI
Conductor (see technical data, Table 1):
calculated separation distance ≤ equivalent separation distance.
If this is not the case, measures according to section 9 or 10 have to be taken.
The length for calculating the separation distance "s" has to be measured from the head piece (see Fig.
1, page 3) to the next level of lightning equipotential bonding, e.g. the earth-termination system.
Outer sheath
Equivalent
separation distance
Outer diameter
Minimum bending radius
Permanent temperature range (in case of permanent installation)
Ambient temperature and conductor temperature
(during installation and processing)
Maximum tensile load
Inner conductor Cu solid / stranded
Table 1
Technical data of the HVI
®
Conductors require special know-how.
Air
Solid materials
®
Conductor
2
®
Conductor and a
Colour
black
grey
RAL 9011
RAL 7035
≤ 75 cm
≤ 150 cm
20 mm
23 mm
200 mm
230 mm
-30° bis +70°C
-5° bis +40°C
950 N
19 mm²
1811_MO_1012_DE_GB_063061