Manual commissioning
When automatic commissioning fails or when multiple devices are connected, manually
commission the device as follows:
Addressing
1. Connect SSA-DNT or ABT to the controller and activate the online commissioning
function.
2. Load web page "KNX PL-Link identification".
Activate the identification function.
a The controller now waits for a signal from the device.
3. On the device, simultaneously press buttons 1 and 8 for at least 5 seconds.
a The "Engineering" page is displayed.
4. Press button 2.
a The display changes from "DISABLE" to "ENABLE".
a The tool identifies the currently active-device and assigns it.
5. After the device is commissioned, change from programming mode to "DISABLE" by
pressing button 2.
Connection test
1. Press button 3 to test the KNX PL-Link connection.
a The display shows the result of the connection test ("DONE" or "FAIL").
2. Press button 8 to return to the engineering page.
Reset to factory settings
NOTICE
This operation resets all user-defined data and configuration settings to factory default
This operation is irreversible.