Siemens QFA1000 Installation Instructions

Room hygrostats

Advertisement

Quick Links

QFA1000, QFA1001 Room Hygrostats
Product Description
These instructions explain how to install a QFA1000
or QFA1001 Room Hygrostat.
Product Numbers
QFA1000 Internal Setpoint
QFA1001 External Setpoint
Required Tools
7 mm flat-blade screwdriver
Phillips head screwdriver
Two 6 × 32 screws
Electric drill
Expected Installation Time
10 minutes
Prerequisites
The base has cable entries at the rear for mounting
the room hygrostat on recessed conduit boxes. For
wall mounting, appropriate holes at the top or bottom
can be knocked out.
Mounting Location
The hygrostat should be mounted:
on an inner wall approximately 4.9 feet
(1.5 m) above the floor, and at least 1.6 feet
(0.5 m) from the closest adjoining wall.
where there is a natural circulation of room
air (do not mount near drafts, in corners,
behind curtains, too close to doors and
windows, or on an outer wall).
away from sources of heat and refrigeration
(radiators, computers, televisions, concealed
heating pipes, hot or cold water pipes).
where it is not exposed to direct sunlight.
Item Number 129-604, Rev. AA
Installation Instructions
Figure 1. Recommended Mounting Locations.
Installation
1.
Using a 7 mm flat-blade screwdriver, insert the
blade into one of the slots on the side of the
housing base. Pry the base away from the
housing cover.
2.
Do the same for the second slot, so that the
cover loosens from the housing base.
3.
Flip open the hygrostat cover.
1
Figure 2. Opening the Unit.
4. Before mounting the hygrostat, run the cable
through the back of the housing, and terminate
the lead wires appropriately, based on how the
unit is intended to operate (either switching on
humidification or on de-humidification). See
Figures 4 and 5.
Document No. 129-604
July 13, 2010
3
2
0.27
(~7 mm)
Page x of x

Advertisement

loading

Summary of Contents for Siemens QFA1000

  • Page 1 Installation Instructions Document No. 129-604 July 13, 2010 QFA1000, QFA1001 Room Hygrostats Product Description These instructions explain how to install a QFA1000 or QFA1001 Room Hygrostat. Product Numbers QFA1000 Internal Setpoint Figure 1. Recommended Mounting Locations. QFA1001 External Setpoint Installation...
  • Page 2 Figure 3. Wiring Diagrams Figure 5. Dehumidification. Var. 1 Var. 2 max. Ø 0.27 Var. 1 (max. Ø 7 mm) Var. 2 max. Ø 0.39 (max. Ø 10 mm) Figure 6. QFA1001 Pictured. Page 2 of 3 Siemens Industry, Inc.
  • Page 3 3. Device will be activated when wiring is terminated to the controller. = 90 H% = 55 H% = 80 H% – Figure 7. QFA1000 Setpoint Setting. QFA1001: Replace cover, aligning external setpoint knob to internal setpoint. Adjust setpoint. Figure 8. QFA1001 Setpoint Setting.

This manual is also suitable for:

Qfa1001