Refrigerant Connections; Airfl Ow Performance [Cfm Vs Pressure Drop] - Bosch BMAC2430ANTD Installation Manual

Multi-position cased coils cooling and heat pump compatible
Table of Contents

Advertisement

1 2 | Bosch Multi-Position Cased Coils

5 Refrigerant connections

NOTICE:
Gently remove the sealing plug of vapor line, use one wrench
to fix the valve base, loosen the nut with another wrench,take
out the flange pad and and sealing ring. The nitrogen pressure
is about 10 PSIG.
To prevent refrigerant leak, use proper tools to ensure clean, burr-free cut.
NOTICE:
TXV bulb MUST be protected (wrapped with wet rag) or
removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and
performance of the comfort coil.
Use brazing shield when brazing close to the cabinet surface and wet rag to protect
rubber grommet. Brazing alloy should be at least 5% silver content.
5.1 Airfl ow performance [CFM vs pressure drop]:
Model
BMAC2430ANTD
BMAC2430BNTD
BMAC2430CNTD
BMAC3036ANTD
BMAC3036BNTD
BMAC3036CNTD
BMAC4248BNTF
BMAC4248CNTF
BMAC4248DNTF
BMAC4860CNTF
BMAC4860DNTF
Table 2
Pressure drop for cooling and heat pump coils
*Data based on wet coil with entering air at 80°F DB / 67°F WB without air fi lter.
Data subject to change
0.05
0.1
0.15
307
485
618
327
527
682
360
585
748
307
485
618
327
527
682
360
585
748
456
638
810
505
726
932
533
857
1105
439
699
906
466
764
978
Pressure Drop (Inches of Water)
0.2
0.25
729
823
810
925
893
1019
729
823
810
925
893
1019
953
1077
1098
1244
1319
1509
1071
1224
1157
1313
Installation Manual
0.3
0.35
0.4
911
991
1063
1024
1122
1217
1132
1238
1348
911
991
1063
1024
1122
1217
1132
1238
1348
1191
1284
1390
1375
1494
1604
1675
1824
1956
1362
1487
1589
1466
1590
1695
03.2017 | Bosch Thermotechnology Corp.