LG AB-H366GSA0 B36AH SG0 Product Data page 30

Ceiling concealed duct (50hz, r410a)
Table of Contents

Advertisement

50Hz • R410A • Heat Pump
50Hz • R410A • Heat Pump
13.4 Wiring Connection
1) Connecting cables
I Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
I 24k Btu
• Cooling & Heating type
Terminals on the indoor unit
Terminals on the outdoor unit 1(L) 2(N)
I 30k/36k/42k Btu
• Cooling & Heating type
Terminals on the indoor unit
Terminals on the outdoor unit
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm
clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the mid-
dle of live pin on the power plug should be over 1.8m.
WARNING
Make sure that the screws of the terminal are free from looseness.
3(L) 4(N)
5
6
7
3
4
5
1
2
3
4
5
1
2
3
4
5
CAUTION
NORMAL CROSS-SECTIONAL AREA
Capacity
1Phase
2
24k Btu/h
5.5mm
2
30k/36k/42k Btu/h
8.5mm
cable(thinner cable) on the clamp and tighten it with a plastic
2
(220V~240V~)
1(L)
2(N)
POWER INPUT
36K/42K Btu/h
(220~240V~)
1(L)
2(N)
POWER INPUT
The connecting cable connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
AREA 1.25mm
Ceiling Concealed Duct
Installation
2
24k/30k/36k/42k Btu/h