DESCRIPTION:
®
The 00e
series 0018e
circulator is a variable speed wet rotor circulator with an ECM, permanent magnet
TM
motor. Operating modes include infinitely variable fixed speed, constant pressure, proportional pressure,
and activeADAPT
self-adjusting proportional pressure
TM
0018e
ECM Circulator Mobile App using Bluetooth
TM
high-efficiency motor reduces power consumption by up to 85% compared to equivalent AC permanent split
capacitor circulators.
APPLICATION:
• Maximum operating pressure: 125 psi (8.6 bar)
• Maximum water temperature: 230°F (110ºC)
• Electrical specifications:
Voltage: 110-120V, 50/60 Hz, single phase
Maximum operating power: 44W
Maximum amp rating: 0.54
• Equipped with a cast iron casing and should be used for closed loop systems only
• Not suitable for open loop potable water or chilled water systems
• Taco circulator pumps are for indoor use only – employer uniquement a l'interieur
• Acceptable for use with water or maximum of 50% water/glycol solution
FEATURES:
• 3 operating modes in dial activation:
- Proportional pressure ( TRV - Panel Radiator ), variable speed - 2 variable pressure
differential settings (Med or High)
- Constant pressure ( ZV - Zone Valve ), variable speed - 2 constant pressure
differential settings (Med or High)
- Fixed speed ( ZONE CIRC - zoning with circulators ) - infinitely adjustable MIN/MAX settings
• 4 operating modes in 0018e
- Fixed Speed - infinitely adjustable MIN/MAX settings
- Constant Pressure - variable speed - 9 constant pressure differential settings
- Proportional Pressure - variable speed - 9 variable pressure differential settings
- activeADAPT
to system conditions
• Multi-color LED display showing operating mode and error code diagnostics
• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation
• Nut capture feature on flanges for easier fit up
• Dual electrical knockouts and 6" stranded wire leads for easy wiring
• Double insulated - no ground-wire required
• Whisper quiet operation
• BIO Barrier
®
protects the pump from system contaminants
• SureStart
- automatic unblocking and air purging mode
®
• Optional 2-way flange model for easy fit-up to any flange orientation
• Integral Flow Check (IFC
) included - Field installed
®
INSTALLATION:
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the warranty. Consult factory for fluid
compatibility.
ATTENTION: L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie. Consultez
le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation and flashing. Premature failure
may result. Adjust expansion tank pressure to equal fill pressure. A larger size expansion tank may be required.
ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi au minimum afin
d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression du réservoir d'expansion de façon qu'elle soit
égale à la pression de remplissage. Un réservoir d'expansion d'une taille supérieure peut être nécessaire.
Instruction Sheet
0018e
ECM High-Efficiency Circulator
TM
Featuring Bluetooth
Adjust the operating mode with the dial or the Taco
.
®
connectivity on your smartphone or tablet. The ECM
Mobile App activation:
TM
- Designed for constant circulation systems. Automatically adjusts
TM
Communication
®
102-557
EFFECTIVE: March 22, 2019
Figure 1:
Standard flange model: 0018e-F2
Part #: VR1816-HY2-FC2A01
Optional 2-way flange model: 0018e-F4
Part #: VR1816-HY2-4C2A01
1

Advertisement

loading

Summary of Contents for Taco 0018e Series

  • Page 1 CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the warranty. Consult factory for fluid compatibility. ATTENTION: L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
  • Page 2 • AIR PURGING SEQUENCE BY ZONE EXPANSION VI, V2, V3 = SHUT-OFF ISOLATION VALVE TANK LAST FIRST P = TACO CIRCULATOR WITHOUT IFC INSTALLED FF = FAST FILL BOILER FEED VALVE • AIR PURGING SEQUENCE BY ZONE EXPANSION PV4 = PURGE VALVE TANK...
  • Page 3 Typical Variable Speed Applications: • Zone Valves • Panel Radiation with Across a Series Thermostatic Valves Loop System Using • Radiant Loops with Zone Valves Actuators - Varies speed to Outdoor Sensor maintain proportional or constant pressure Across Multi-Zone differential (∆P) Radiant Manifolds with Loop Actuators Boiler...
  • Page 4 Play on your mobile device. Download the Taco 0018e ECM Circulator mobile app for free and install it on your mobile device. Once complete, you are able to start using the app. Additional operating instructions can be found on the app itself.
  • Page 5: Performance Curves

    0018e PERFORMANCE CURVES TRV - PANEL RADIATOR MODE Variable Speed ZV - ZONE VALVE SYSTEM MODE Variable Speed In Zone Valve - Constant pressure mode, the circulator maintains a constant pressure differential (∆p- c) in the system as heating load increases or decreases.
  • Page 6 7. Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction. CONTROL FAULTS CAUSES REMEDIES PANEL Increase the system suction Suction pressure is LED on pressure within the insufficient - cavitation The circulator is permissible range.
  • Page 7 Terminal box cover screws (5 per bag) 0010-025 RP Integral Flow Check (IFC ® 007-007 RP Flange gasket set 0018e Pump Cross Reference (Fixed Speed Mode): SPEED TACO GRUNDFOS WILO B & G/XYLEM ARMSTRONG Minimum Compass (1) Alpha 15-55 (Low)
  • Page 8: Limited Warranty Statement

    If in doubt as to whether a particular substance THE ABOVE WARRANTIES ARE IN LIEU OF the date code. is suitable for use with a Taco product or part, or ALL OTHER WARRANTIES, EXPRESS OR In order to obtain service under this warranty, it...

This manual is also suitable for:

00e series0018e-f20018e-f4