How To Reset The Inverter To Factory Defaults - Bosch Rexroth EFC 3600 Easy Start Manual

Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

Easy Start Guide
Bosch Rexroth EFC 3600 Series Inverter

13. How to reset the Inverter to Factory Defaults

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
13.1 Select the b0 Parameter Group
With the motor stopped, press the "Func" button
repeatedly until the display shows "-b0-" (do not press
and hold the "Func" button).
13.2 Select Parameter b0.05.
Press the "Set" button to select the b0 Parameter group
then use the up button to locate parameter b0.05.
13.3 Change value of b0.05 from 0 to 1.
Press the "Set" button to edit the value of b0.05 and use
the up button to change this from 0 to 1.
Press the "Set" button again to save the changes.
13.4 Finished
The display will show the next parameter for editing
(b0.06).
Press the "Function" button twice to exit from the
parameter menu.
Optional: repeat the process and change b0.05 from 0 to
2 to clear recent fault messages if required.
©