Easy Start Guide
Bosch Rexroth EFC 3600 Series Inverter

11. How to configure "3-Wire" control with Run/Stop

pushbuttons and Forward/Reverse selection

The parameters described in Section 5 enable
Run/Stop operation via the red and green
buttons on the Inverter.
If this is unsuitable for the application, remote
switches can be used instead.
11.1 Parameters to change for remote 3-wire control
Parameter Description
b0.02
Access to additional parameters
b1.02
First RUN Command Source
E0.03
Terminal X3 program
E0.00
2-wire / 3-wire control
E0.01
Terminal X1 program
E0.02
Terminal X2 program
X1
2
EFC 3600
I/O Terminal
Blocks
2
1
Pushbutton
Normally Open
"Run"
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
How to set
Default is 0 for Basic Parameters. Set at
Set to
1
Set to
7
Set to
2
Set to
23
Set to
24
X2
X3
SC
4
3
1
3
1
Pushbutton
Switch, 2 Position
Normally Closed
Normally Open
"Stop"
"Forward / Reverse"
This section explains how to enable 3-wire
control with Run and Stop commands via
separate pushbuttons and Forward/Reverse
selection via a selector switch. Note that once
this procedure is complete, the Run/Stop
buttons on the Inverter can no longer be used.
for IO Terminals on the Inverter
for 3-wire running control on X3
for 3-wire control with Forward/Reverse selection
for run forward command on X1
for run reverse command on X2
11.2 Connecting the Switches
A wiring diagram is shown in the illustration
opposite. The SC terminal is a common
connection for terminals X1-X5 and has no
other function.
For "Run" and "Stop", two suitable
pushbuttons should be installed. The "Run"
pushbutton should include a Normally Open
contact between terminals SC and X1 and the
"Stop" a Normally Closed contact between
terminals SC and X3.
For "Forward/Reverse" a suitable 2 position
NO (
Normally Open
between terminals SC and X2.
4
1
A momentary connection between SC and X1
will start the motor. It will continue to run until
R
the connection between SC and X3 is broken.
Note that the Forward/Reverse switch only
selects the direction of rotation - it will not start
or stop the motor.
requires the motor to turn in one direction, the
Forward/Reverse switch can be omitted.
©
The Inverter
2
to enable Extended Parameters.
) switch should be installed
If the application only
Page 11