517/2014. The tightness test must be documented in the log. - Never interrupt the power supply, even outside the heating season. The system's active frost pro- tection is not guaranteed if the power supply is interrupted. www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
CAUTION Failure to observe this information may result in non-seri- standard shown in the heading of this chapter. ous or minor injury. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
- Still extracts heat from the outdoor air at - 20 °C outside temperature. Note For centralised control of the heating system, you would need the WPM heat pump manager. www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
The tightness test must be documented in the log. front top, on the right or left hand side of the casing. Example Montageanweisung beachten! Dichtheit geprüft! Made in Germany 1 Number on the type plate | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
If the air discharge side of the appliance faces a wall of a house, the cool air from the air discharge may cause condensate to form on this wall. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Only use weather-resistant cables. Heat pump manager WPM A WPM heat pump manager is required to operate the appliance. This controls the heat pump and regulates the heating system. www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
"SETTINGS / HEATING / STANDARD SETTINGS", set param- eter "BUFFER OPERATION" to "ON". The flow rate can be adjusted using the temperature differential of the buffer circuit. The value must not fall below the minimum flow rate. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Route the electrical cables through the cable entries with strain reliefs. f Check the function of the strain relief fittings. www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
In the case of temporary faults, the output switches the signal through for a specific time. In the case of faults that result in a permanent appliance shutdown, the output switches through permanently. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 13
Secure the reversing hoods with two screws each. f Secure the side plinth trims by hooking into the appliance frame. f Secure the front and back plinth trims by hooking into the side plinth trims. www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
If you raise the "HEATING CURVE" parameter, adjust the zone valve or thermostatic valve in the lead room to the required temperature when outside temperatures are high. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
If the heat pump and frost protection are completely switched off, drain the system on the water side. 1 LEDs 2 Reset button 3 DIP switch (WP-Typ) 4 DIP switch (BA) www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
If the IWS was incorrectly initialised, the settings can be reset with this button. For this also observe the chapter "Reinitialising IWS" in the heat pump manager operating and installation instructions. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 22
Flow temperature 45 °C Flow temperature 55 °C Power consumption Power consumption [KW] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 23
Specification Coefficient of performance (COP) Coefficient of performance ε [-] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
Flow temperature 45 °C Flow temperature 55 °C Power consumption Power consumption [KW] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 25
Specification Coefficient of performance (COP) Coefficient of performance ε [-] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
Flow temperature 45 °C Flow temperature 55 °C Power consumption Power consumption [KW] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 27
Specification Coefficient of performance (COP) Coefficient of performance ε [-] Inlet temperature of the WQA medium [°C] Flow temperature 35 °C Flow temperature 45 °C Flow temperature 55 °C www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
Max. operating current Versions Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu Refrigerant R407 C R407 C R407 C Defrost type Circuit reversal Circuit reversal Circuit reversal IP rating IP14B IP14B IP14B Refrigerant charge | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Page 29
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 K m³/h 3.75 4.90 Nominal heating flow rate at A2/W35, B0/W35 and 7 K m³/h 3.66 Flow rate, heat source side m³/h 7000 7000 7300 www.stiebel-eltron.com WPL 34 | WPL 47 | WPL 57 |...
Page 30
This device is filled with refrigerant R407C. Refrigerant R407C is a CFC greenhouse gas mentioned in the Kyoto protocol with a global greenhouse potential (GWP) = 1653. Never release refrigerant R407C to atmosphere. | WPL 34 | WPL 47 | WPL 57 www.stiebel-eltron.com...
Need help?