3.7 Switching the Primary Return Flow

(fig. 15)
When the RATIOfresh freshwater unit is used in systems
that are continuously operated at water temperatures >=
60 °C and work with circulation nets, we recommend the
controlled switching of the return flow to the buffer cylin-
der. Thus it can be avoided that during periods of low hot
water drawing, hot water enters the lower part of the the
buffer cylinder where it could cause unwanted mixing.
The switching can be carried out by a 3-way valve (see solu-
tion shown in fig. 15). The valve should have short switching
times (<30 s) and low pressure loss. (e.g. Wagner & Co 3-
way-valve, order no. 160 101 44). Control should be based
upon temperature difference, e.g. via solar controller
SUNGO SXL.
3.8 Connecting the Controller (fig. 9)
All tasks and activities involving the transport, installation,
as well as operation and servicing must be performed by
qualified technical personnel.
The controller is for the most part prewired. A fourth tem-
perature sensor and a circulation pump can be connected
in addition to the mains connection. If the disinfection func-
tion is utilized, the auxiliary heating of the buffer cylinder
must be activated via the external switching output.
To open the controller turn the 4 Phillips screws (cf. 10-9)
to the left by 90° and remove cover of housing. Remove
the flat ribbon cable plug to the display board from
socket (3) and set aside the cover of the controller to
avoid damaging it.
Remove the plug (4) to the mains connection from
socket (5), route the mains cable (cable cross-section 3 x
0.75 to 1.5), e.g. along the primary return and a free PG
gland (cf. 10 no. 10), into the station. Attach phase, zero
conductor, and potential ground to plug (4) and then in-
sert this plug into socket (5).
If needed, connect the circulation pump with plug (6) in
the same way and plug into socket (7) (required cable
cross-section: 3 x 0.75 to 1.5).
A fourth temperature sensor (type KTY, cf. accessories)
can be connected via plug (8) and socket (9).
A RS 232 interface cable available as an accessory can
be connected to plug (12) (socket (13)). It is also possi-
ble to log all measured values, the current controller sta-
tus, and the current pump output. This requires connect-
ing the 9-pin D-SUB plug of the data cable to the serial
RS 232 interface of a computer. Possible logging utilities
are a terminal program such as included with Windows
95, 2000, or XP (All Programs -> Accessories). Use these
transfer settings: RS 232 Port = COM1/COM2, Emula-
tion = ANSI, Transfer rate = 19200 bit/s, Data bits = 8,
Stop bits = 1, Parity = None, Protocol = No protocol
(XON/XOFF, RTS/CTS).
The additional external switching output of the
RATIOfresh freshwater station on plug (14) socket (15) is
intended for the activation of the aux. boiler heating for
the disinfection operation. Please note that the current
applied to this potential-free switching contact may not
exceed a current intensity of max. 0.5 A. If a boiler de-
mand is triggered, the controller closes contact 11-12
EN-RATIOfresh-250-400_TI-MA-0809-11214900
and opens contact 11-13. Once the boiler is no longer
needed, contact 11-12 is opened again and contact 11-
13 is closed again. If contact 11-12 is closed, the third
LED from the left (cf. 10-3) is continuously green.
fig. 9 also depicts the control fuse (16) (400mAT / 250 V)
and the output fuse (17) (6.3 AT / 250 V).
Hold controller housing cover before the bottom sec-
tion of the housing, reattach the flat ribbon cable to the
display board (3), attach the cover to the bottom section,
press down the 4 Phillips screws (cf. 10-9) and turn to-
wards the right by 90°.
3.9 Closing the Housing (fig. 8)
To close the metal housing, insert the housing cover (1) into
the snap-in groove (2) at the bottom section of the housing
(3) and then snap the two snap-in plugs (4) at the bottom
into sockets (5).
2
3
5
5
4
Figure 8 Close housing
1 Housing cover; 2 Snap-in groove; 3 Bottom section of housing;
4 Snap-in plug; 5 Snap-in socket.
1
4
11