9. Insert the bottom of the new FFT board in the slot located in the bottom right of the mounting bracket as indi-
cated in illustration below.
10. Secure the module to the mounting bracket standoffs with the two mounting screws.
11. Wire the terminal blocks TB1, TB2 and TB3 as described in the illustration below. Plug the terminal block
connectors which were disconnected in step 2 into TB1, TB2 and TB3 located on the top edge of the FFT.
12. Plug the panel telephone handset into Phone Jack J1 on bottom center of FFT.
13. Set switch SW1 to correct position. SW1 positioned to the left (as illustrated below) indicates that the remote
microphone is installed. SW1 positioned to the right indicates that a remote microphone is not installed.
14. Set switch SW2 to correct position. SW2 positioned up (as illustrated below) indicates that the audio wiring to
the Remote Page Jack is configured for 2-wire Class B.
15. Reapply AC and DC power
16. Program the host FACP for proper operation with the Audio Panel
17. Test the panel for proper operation.
Terminal Block Connectors
TB3
TB2
TB1
J1
SW1
FFT
SW2
Ribbon Cable
Connectors
J2 (on side)
J3 (on back)
Document 52246 Rev A ECN 07-873 1/16/08
Standoff
Standoff
Slot
Mounting Bracket