Quick Installation Guide
AM Series
Venting/Air Intake
ACCEPTABLE MATERIALS
• Acceptable vent materials: Al29-4C Stainless Steel, Polypropylene, CPVC, PVC. For Alcove/Closet Installation, use Al29-4C only.
• Do not use PVC exhaust for applications where return water temperature > 145F. See O&M for additional information.
• Polypropylene and Al29-4C exhaust requires additional adapters - contact the vent manufacturer for suitable adapter.
• Vent material must be sealed to specification of its manufacturer. Do not use EPDM seals.
VENT/AIR INTAKE SIZING:
• Maximum length of vent is 60 equivalent ft.
• Maximum length of air intake is 60 equivalent ft.
• For manifolded vents, see O&M manual
Equivalent Pipe Lengths
Diam
Sharp 90°
AM 199/250
3"
10 ft.
Diam
AM 399/500
4"
10 ft.
AM 750/1000 6"
10 ft.
AM 199/250
3"
Exhaust Adapter supplied with unit accepts
AM 399/500
4"
PVC. When using polypropylene or Al29-4C
exhaust, additional adapter required—
example manufacturers:
AM 750/1000
6"
Exh Outlet
AM 199/250
3"
• Maximum length of air intake is 60 equivalent ft.
AM 399/500
4"
• For manifolded vents, see O&M manual
AM 750/1000
6"
AM 199/250
3"
AM 399/500
4"
AM 750/1000
6"
Security Chimneys (Al29-
AM 199/250
3"
AM 399/500
4"
AM 750/1000
6"
Security Chimneys DW
AM 199/250
3"
AM 399/500
4"
AM 750/1000
6"
QIG-0001_0A •
Sweep 90°
45°
Equivalent Pipe Lengths
5 ft.
5 ft.
Sharp 90° Sweep 90°
45°
5 ft.
5 ft.
5 ft.
5 ft.
10 ft.
5 ft.
5 ft.
10 ft.
5 ft.
5 ft.
10 ft.
5 ft.
5 ft.
Duravent PolyPro
3PPS-03PVCM-3PPF
4PPS-04PVCM-4PPF
6PPS-06PVCM-6PPF
Centrotherm Innoflue
(PP)
ISAAL03
ISAAL04
ISAAL06
4C)
SS3PVCU
SS4PVCU
SS6PVCU
(Al29-4C)
SS3PVCUK
SS4PVCUK
SS6PVCUK
11/1/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
VENT TERMINATION
LOCATIONS
Page 2 of 7

Advertisement

loading

This manual is also suitable for:

Aerco am 199Aerco am 500Aerco am 250Aerco am 750Aerco am 1000Aerco am 399