Operating Limits - Lennox AIRCOOLAIR ASC Series Application Manual

Large ducted split 19-134 kw, air cooled condensing unit 20-230 kw
Table of Contents

Advertisement

PERFORMANCES - CONDENSING UNIT
EXTRA POWER CONSUMPTION
Cooling and heating modes
MODELS
FP1
Low speed
FP1
High speed

OPERATING LIMITS

Cooling only units
Indoor temperature
Cooling operation
Outdoor temperature
Heat pumps
Indoor temperature
Cooling operation
Outdoor temperature
Indoor temperature
Heating operation
Outdoor temperature
DB : Dry bulb temperature
WB : Wet bulb temperature
Application Guide • AIRCOOLAIR-AGU-1603-E
100D
120D
2
2
6.2
6.2
Maximum temperatures
32°C DB / 23°C WB
45°C
(020S-025S-030S-045D-055D)
47°C
(035S-040S-070D-085D-100D-
120D-140D-200D-230D)
Maximum temperatures
32°C DB / 23°C WB
45°C
(020S-025S-030S-045D-055D)
47°C
(035S-040S-070D-085D-100D-
120D-140D-200D-230D)
27°C DB
Depending on models
See heating capacities tables
(*) : With optional 0°C low temperature kit
(**) : With optional -15°C low temperature kit
140D
200D
1
5.8
5.2
14.2
Minimum temperatures
21°C DB / 15°C WB
+10°C (standard unit)
0°C (*)
-15°C (**)
Minimum temperatures
21°C DB / 15°C WB
0°C
15°C DB
-10°C DB / -11°C WB
230D
2
10.4
• 43 •