Weil-McLain SVF 1500-3000 Series User's Information Manual page 3

Commercial condensing gas-fired water boilers.
Table of Contents

Advertisement

SVF
Series 1
Commercial Condensing Gas-Fired Water Boiler - User's Information Manual
STOP! READ THIS BEFORE PROCEEDING . . .
Failure to adhere to the guidelines on this page
can result in severe personal injury, death or
substantial property damage.
Boiler service and maintenance —
J To avoid electric shock, disconnect all electrical supplies to
the boiler before performing maintenance if wiring will be
exposed.
J To avoid severe burns, allow boiler to cool before performing
maintenance.
J You must maintain the boiler as outlined in this manual and
have the boiler started up and serviced at least an-
by a quali ed service technician to ensure boiler/
nually
system reliability.
Boiler operation —
J Do not block ow of combustion or ventilation air to boiler.
is boiler is equipped with a control which will automatically
shut down the boiler should air or vent be blocked. If vent or
air blockage is easily accessible and removable, remove it. If
the boiler display indicates a manual reset lockout, follow the
procedure on Figure 8, page 8 to reset the boiler. (If blockage is
not obvious or cannot be removed, have the boiler and system
checked by a quali ed service technician.)
J Do not allow contaminated air to enter the boiler room (or air
inlet pipe if direct vented). See page 9 for details.
J Should overheating occur or gas supply fail to shut o , do
not turn o or disconnect electrical supply to boiler. Instead,
shut o the gas supply at a location external to the appliance.
J Do not use this boiler if any part has been under water. Im-
mediately call a quali ed service technician to inspect the
boiler and to replace any part of the control system and any
gas control, which has been under water.
If any part of a boiler, burner or its controls
has been sprayed with or submerged under
water, either partially or fully, DO NOT attempt
to operate the boiler until the boiler has
been either replaced or completely repaired,
inspected, and you are sure that the boiler
and all components are in good condition
and fully reliable.
boiler, you will cause a re or explosion hazard,
and an electrical shock hazard, leading to serious
injury, death, or substantial property damage. See
the instructions at right.
Part number 550-100-251/0819
Otherwise, by operating this
Boiler water —
J Have boiler water chemistry checked at least annually by a
quali ed service technician.
J DO NOT use petroleum-based cleaning or sealing com-
pounds in boiler system. Gaskets and seals in the system may
be damaged.
is can result in substantial property damage.
J DO NOT use "homemade cures" or "boiler patent medi-
cines". Serious damage to boiler, personnel and/or property
may result.
J Continual fresh makeup water will reduce boiler life. Mineral
build-up in boiler heat exchanger reduces heat transfer, over-
heats the metal, and causes heat exchanger failure. Addition
of oxygen can cause internal corrosion in system components.
Leaks in boiler or piping must be repaired at once to prevent
makeup water.
J Do not add cold water to hot boiler.
boiler heat exchanger to crack.
Frozen Water Damage Hazard
Residences or buildings that are unattended in severely cold
weather, boiler system components failures, power outages, or
other electrical system failures could result in frozen plumbing
and water damage in a ma er of hours. For your protection, take
preventative actions such as having a security system installed
that operates during power outages, senses low temperature, and
initiates an e ective action. Consult with your boiler contractor
or a home security agency.
e exposure of boiler components to
Saltwater Damage
saltwater can have both immediate and long-term e ects. While the
immediate e ects of saltwater damage are similar to those of fresh-
water (shorting out of electrical components, washing out of critical
lubricants, etc.), the salt and other contaminants le behind can lead
to longer term issues a er the water is gone due to the conductive
and corrosive nature of the salt residue.
equipment contaminated with saltwater or polluted water will no
longer be covered under warranty and should be replaced.
If any
Electrical Damage
came into contact with water, or was suspected to have come into
contact with water, replace the boiler with a new Weil-McLain boiler.
ermal shock can cause
erefore, Weil-McLain
or
electrical component
wiring
3