Connections - Technibel CSCV 152 LL Installation Instructions Manual

Console type split system for low temperature rooms
Table of Contents

Advertisement

4 - CONNECTIONS

1 - Gas refrigerant connection.
2 - Liquid refrigerant connection.
3 - Electrical connection.
4 - Condensate drainage.
5 - Mains supply with isolating and protective device.
6 - Remote control (accessory).
4.1 - CONNECTION OF THE CONDENSATE LINES
4.1.1 - VERTICAL MOUNTING
• Use the 12 mm dia. x 16 mm hose supplied.
• Pass it with refrigerant pipes through one of the covers and connect it to
a pipe of minimum internal diameter 12 mm, respecting a slope in the
liquid's flow direction.
4.1.2 - CEILING MOUNTING
• Use the copper pipe and the end piece supplied.
4.2 - REFRIGERANT CONNECTION
• If the difference in level is greater than 3 metres,
make an oil trap.
NOTE: Nominal cooling capacity is given for a total
pipe length of 8 m.
For pipe lengths over the maximum length, please
consult us.
Dia. of pipes
Gas
CSCV 152 LL
3/8"
CSCV 202 LL
3/8"
CSCV 302 LL
1/2"
CSCV 402 LL
1/2"
R 40 7 C
• Fluid R 407 C, as opposed to R22, is not a pure fluid but
a blend composed of:
- 23% R 32 + 25% R 125 + 52% R 134 A.
• The compressors approved for operation with this fluid
are filled beforehand with polyalcohol oil.
Contrary to mineral oil, it is very hygroscopic: it absorbs
the humidity of the ambient air very quickly. This can
modify its lubricant properties and lead in time to the
destruction of the compressor.
MAINTENANCE INSTRUCTIONS
1 - Never add oil to the appliance; the compressor is filled
with polyalcohol oil, a special oil which cannot tolerate
the presence of other oils.
2 - The instruments used for:
- filling,
- pressure measurements,
- emptying under vacuum,
- recovering the fluid,
must be compatible and only used for the R 407 C fluid.
3 - The weight of the refrigerant contained in the storage
bottle must be checked constantly. Do not use it from
the moment the remaining weight is less than 10% of
the total weight.
6
Maximum
permissible
permissible
length
difference in
Liquid
A (m)
level B (m)
1/4"
15
1/4"
15
1/4"
20
1/4"
20
APPLIANCES FILLED WITH R 407 C
Oil
trap
Maximum
Refrigerant
load
in the GRV
(g)
7
730
7
800
7
750
1 660 1-phase
7
1 680 3-phase
4 - In the case of a new charge:
- do not use the charging cylinder,
- use a balance and a dip pipe type R 407 C cylinder,
- charge the weight of R 407 C as per the value indicated
on the unit's identification plate (for "split systems",
refer to the installation instructions as the charge must
consider the length of the connecting lines),
- IMPORTANT: see paragraph 3.
5 - The charge must be undertaken in liquid phase.
6 - In case of leakage, do not complete the charge: recover
the remaining refrigerant for recycling and perform a total
charge.
Recovery, recycling or the destruction of the fluid must be
done in compliance with the laws in force in the country
concerned.
7 - If the refrigerant circuit is opened, you must:
- avoid the entry of air into the circuit as much as
possible,
- replace the filter drier,
- perform the "vacuum operation" at a minimum level of
0.3 mbar (static).
6
5
TAV
4
3
Ceiling mounting
End piece
Copper pipe
A
B
Addition of
refrigerant
above
(m)
8
8
4
8
GRV
2
1
Hose
A
B
Quantity of
refrigerant to
be added
(g/m)
15
15
25
25