TROUBLESHOOTING.

Attention:
- Incorrectly managing thermostats, safety valves
and/or other types of valves can cause the tank
to break. Every operation on the unit must be
done scrupulously following the instructions
that concern it.
- The electrical supply voltage must always be
cut off before cutting off the hydraulic supply.
- Regularly check safety valve operation, making
it open to make sure water flows out with no
problem.
Code
101
CONTROL KIT/OUTDOOR UNIT wiring error
201
CONTROL KIT/OUTDOOR UNIT communication error (coupling error)
202
CONTROL KIT/OUTDOOR UNIT communication error (3 min.)
203
Communication error between INVERTER and MAIN MICOM (6 min.)
221
OUTDOOR UNIT temperature sensor error
231
Condensation temperature sensor error
251
Flow temperature sensor error
320
OLP sensor error
403
Ice detected on the compressor during operation in cooling
404
OUTDOOR UNIT overload prevention trip (at Safety device start-up, operation ? normal)
416
Compressor flow overtemperature
419
OUTDOOR UNIT EEV operation error
425
One of the supply voltage phases has fallen (only for three-phase models)
440
Operation in central heating stopped (outdoor temperature > 36°C)
441
Operation in cooling stopped (outdoor temperature < 9°C)
458
OUTDOOR UNIT fan 1 error
461
Compressor start-up error [Inverter]
462
Absorption error [Inverter]/PFC overcurrent error
463
OLP overheating
464
IPM overcurrent error [Inverter]
465
Compressor voltage limit error
466
LINK in CC Over/Undervoltage error
467
Compressor rotation error [Inverter]
468
Current sensor error [Inverter]
469
LINK in CC voltage sensor error [Inverter]
470
EEPROM reading/writing error
471
OTP error [Inverter]
474
IPM (IGBT Module) or PFCM temperature sensor error
475
OUTDOOR UNIT fan 1 error
484
PCF overload error
485
Incoming current sensor error
500
IPM overload
554
Coolant leak error
- The electrical connections and any work on the
electrical components must be done solely by
qualified electricians.
- The hydraulic connections and any work on the
hydraulic components must be done solely by
qualified installers.
- The components used as spare parts must be
approved by Immergas
Explanation
30 30

11.1 FAULT CODES.

Every problem that presents itself during opera-
tion is highlighted by an error code that appears
on the main board of the outdoor unit or on the
hydronic unit display.