Installation Instructions ArmorBlock MaXum 4 Input Module Series B (Cat. No. 1792D-4BV0D) 41455 This ArmorBlock MaXum™ I/O module (Cat. No. 1792D-4BV0D) is a stand-alone 24V dc I/O product which communicates via a DeviceNet™ network. The sealed housing of this module requires no enclosure.
Programmable Controllers, Part 2 - Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 •...
ArmorBlock MaXum 4 Input Module Series B Install Your ArmorBlock MaXum I/O Module To install the module: • Set the node address • Mount the module to the cable base • Connect the cord sets • Communicate with the module These steps are explained in more detail in the following procedures.
ArmorBlock MaXum 4 Input Module Series B See the illustration of the node address below. NODE ADDRESS (00-63 PGM) Bottom View of Module 30703-M Example: Node Address is set at 62, see small black dots. Install the Module This module mounts to the following cable bases: •...
Page 5
ArmorBlock MaXum 4 Input Module Series B To install the module: Proper alignment of the screws is necessary to IMPORTANT complete the connections between the module contacts and the cable contacts. 1. Position the module over the mounted cable base. Align the three captive screws in the module with the accepting receptacles in the base.
Page 6
ArmorBlock MaXum 4 Input Module Series B Connect the Input Cord Sets to the MaXum Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Four micro caps cover the connectors on your module. Remove the caps and connect your cables to the appropriate ports.
ArmorBlock MaXum 4 Input Module Series B Input connectors for this module are shown below. Connector A Connector D Input 0 Input 3 Connector C Connector B Input 1 Input 2 41461 DeviceNet Cable DeviceNet cables are described in the installation publications for the cable base assembly of your choice.
Page 8
ArmorBlock MaXum 4 Input Module Series B Polled - a master initiates communication by sending its polled I/O message to the module. The 4 input module scans the inputs and fault bits producing a response that reflects their status. Change-of-state - productions occur when an input changes or a fault condition occurs.
ArmorBlock MaXum 4 Input Module Series B Troubleshoot with the Indicators This module has the following indicators: • Network/Module status indicator • Logic status indicator • Individual point status indicators Point indicator Point indicator for for input 3 input 0...
Page 10
ArmorBlock MaXum 4 Input Module Series B The following table describes logic status indicators. Logic Status Indicators State Status Logic is disabled Solid Green Logic is enabled Flashing Green Local forces are applied and local logic is enabled The following table describes I/O status indicators.
ArmorBlock MaXum 4 Input Module Series B Specifications 4 Input Module - Cat. No. 1792D-4BV0D Input Specifications Max. Min. Inputs per block 4 - 3 wire or dry contact PNP or NPN devices Sensor Source Current (per input) 100mA Off-Wire Sense Current 0.5mA...
ArmorBlock MaXum 4 Input Module Series B Hazardous Location Approval The following information applies only to products marked with Hazardous Location Approval, when operating in hazardous locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
Page 13
ArmorBlock MaXum 4 Input Module Series B When used in a Class I, Division 2, hazardous WARNING location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes. Les informations suivantes ne concernent que les produits marqués pour une utilisation en environnements dangereux :...
Page 14
ArmorBlock MaXum 4 Input Module Series B AVERTISSEMENT Utiliser des fils d’alimentation qui conviennent à une température de 30°C au-dessus de la température ambiante. Pour une utilisation en environnement de classe i, AVERTISSEMENT division 2 dangereux, cet equipement doit etre monte dans un boitier avec un cablage approprie conforme aux normes electriques en vigueur.
Page 15
ArmorBlock MaXum 4 Input Module Series B Notes: Publication 1792D-IN017B-EN-P - September 2000...
Page 16
ArmorBlock, ArmorBlock MaXum and KwikLink are trademarks of Rockwell Automation. RSNetWorx for DeviceNet is a trademark of Rockwell Software, Inc. DeviceNetManager is a trademark of Rockwell Automation Allen-Bradley. Inc. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). Publication 1792D-IN017B-EN-P - September 2000 PN 957395-42 Supersedes Publication 1792D-5.17 - October 1998...