8
PositionMaster EDP300 DIGITAL POSITIONER | CI/EDP300-EN REV. D
... 2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
ATEX und IECEx electrical data
Type of protection Ex i, intrinsic safety
Basic device
Signal circuit (AI)
Terminals
Temperature class T1 – T4
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 6.5 nF without pressure option; 8.8 nF with pressure option
i
L
= negligibly small
i
Digital input (DI)
Terminals
Temperature class T1 – T4
U
= 30 V
i
P
= 500 mW
i
C
= 4.2 nF
i
L
= negligibly small
i
Digital output (DO)
Terminals
Temperature class T1 – T4
U
= 30 V
i
P
= 500 mW
i
C
= 4.2 nF
i
L
= negligibly small
i
Option modules
Module for the emergency shutdown function
Terminals
Temperature class T1 – T6
U
= 30 V
i
P
= 1 W
i
C
= 5.3 nF
i
L
= negligibly small
i
Module for analog feedback (AO)
+11 / −12
Terminals
Temperature class T6
Temperature class T1 – T4
U
= 28 V
U
= 30 V
i
i
I
= 320 mA
I
= 320 mA
i
i
P
= 0.8 W
P
= 1 W
i
i
C
= 11.3 nF
i
L
= 150 µH
i
Module for universal input (UAI)
+81 / −82
Terminals
Temperature class T6
Temperature class T1 – T4
U
= 28 V
U
= 30 V
i
i
P
= 400 mW
I
= 320 mA
i
i
P
= 1 W
i
C
= 11.3 nF
i
L
= 150 µH
i
Module for digital feedback (SW1 / SW2)
+83 / −84
Temperature class T6
Terminals
U
= 28 V
i
Temperature class T1 – T4
P
= 400 mW
i
Per output:
U
= 30 V
i
P
= 0.5 W
i
I
= 250 mA
i
C
= 2.2 nF per output
i
L
= negligibly small
i
+85 / −86
Limit switch (Limit 1 / Limit 2)
Limit monitor with proximity switches
Terminals
Temperature class T1 – T4
In accordance with type examination certificate PTB 00 ATEX 2049X
*
No IECEx approval
+31 / −32
Temperature class T6
U
= 28 V
i
I
= 320 mA
i
P
= 0.8 W
i
+21 / −22
Temperature class T6
U
= 28 V
i
I
= 320 mA
i
P
= 0.8 W
i
SW 1: +41 / −42
SW 2: +51 / −52
Temperature class T6
Per output:
U
= 28 V
i
P
= 0.4 W
i
Limit 1: +51 / −52
Limit 2: +41 / −42
Temperature class T6