COMMISSIONING OF THE CROSSFLOW SYSTEM

Potable and Non-Potable Water Circuit
All lines must be flushed of debris prior to filling the system. Failure to observe this requirement may lead to
system blockage and/or underperformance. Check and clean the line strainers after flushing.
Fill the potable water circuit by opening the isolation valve at the cold water inlet connection on the potable
water side of the Crossflow. Open a hot tap so air may be purged from within the system whilst filling. Close
hot tap when all air has been expelled.
Fill the non-potable water circuit by opening the isolation valve at the "Heating Source In" and "Heating
Source Out" connections on the non-potable water side of the Crossflow. Ensure air is purged from within
the system whilst filling.
When full operational pressure is reached, ensure that all connections on both circuits are free of leaks. The
non-potable water circuit MUST BE full and pressurised before any other tests are conducted to avoid
potentially damaging the Crossflow pump. Failure to observe this precaution will result in warranty being
void.
Switch on the electrical power to the Crossflow and follow the instructions below to set the temperature.

SETTING THE DELIVERY TEMPERATURE

The temperature entering the primary side of the Crossflow should
o
be at least 5
C higher than the set temperature of the Crossflow in
order for the Crossflow to perform to specification.
The Crossflow set point temperature should be at least 5
the ECO setting for the given model. Refer to table below for ECO
temperature settings.
The Crossflow is supplied from the factory at the temperature
described in the table below. If adjustment is required:
Go to Home screen on the pump.
Press OK. The setpoint box will be highlighted.
Press OK. The temperature will be highlighted
Press OK. The first digit will be highlighted. Use the Up/Down
and Side keys to select the desired setpoint.
Press the Return key to go back through the pages or the
Home key to return to the home page.
Delivery Skid Temperature Settings
Model
ECO Setting
70
70
Refer to Grundfos Magna manual supplied with Crossflow for other system options.
Copyright Rheem Australia PTY LTD 2016
o
Factory Setting
Max Recommended Temp Setting
65
15
Chapter 3 – Commissioning Procedures
C below
65
Dec 2016 AQ0901085 Rev C