Rheem Crossflow RD200 Owner's Manual And Installation Instructions
Rheem Crossflow RD200 Owner's Manual And Installation Instructions

Rheem Crossflow RD200 Owner's Manual And Installation Instructions

Instantaneous heat exchange delivery system

Advertisement

Owner's Guide
and
Installation Instructions
Rheem Crossflow ™
Instantaneous Heat Exchange
Delivery System
This water heater must be installed and serviced by a qualified person.
Please leave this guide with a responsible officer.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Crossflow RD200 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rheem Crossflow RD200

  • Page 1 Owner’s Guide Installation Instructions Rheem Crossflow ™ Instantaneous Heat Exchange Delivery System This water heater must be installed and serviced by a qualified person. Please leave this guide with a responsible officer.
  • Page 2: Table Of Contents

    SETTING THE DELIVERY TEMPERATURE ....................15 SETTING THE GLOBE VALVE ........................16 CLEANING THE HEAT EXCHANGER ......................17 TROUBLE SHOOTING ............................ 17 THE RHEEM WARRANTY - GENERAL ......................19 Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 3 This water heater may be protected by one or more patents or registered designs. TRADEMARKS ® Registered trademark of Rheem Australia Pty Ltd. Trademark of Rheem Australia Pty Ltd. NOTE: Every care has been taken to ensure accuracy in preparation of this publication.
  • Page 4: Description

    316L stainless steel manifolds and fittings, the steel frame is fully welded and hot dip galvanised for superior corrosion resistance. The Rheem Crossflow is available in four sizes and two of the same size unit can be connected where further redundancy or greater capacity is required.
  • Page 5 *The maximum working pressure of each side of the system will be governed by the lowest operating pressure appliance connected to it. The potable water side (secondary side) must be higher than the non-potable side (primary side). Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 6 Chapter 3 – Commissioning Procedures Crossflow System Dimensions (Dual head pump model shown) Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 7 Table 2 – Crossflow System Output Table 3 – Crossflow System Pressure Drop (Secondary Side) Secondary Side Pressure Drop vs Flow Rate Flow Rate L/s 200kW 400kW 600kW 800kW Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 8 Primary Temp Primary Temp Output (kW) 1570 1200 1070 Output (kW) 1740 1600 1390 1260 Temp Rise Secondary Side Flow Rate (L/min) Temp Rise Secondary Side Flow Rate (L/min) Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 9: System Installation

    It is the responsibility of the plumber/installer that all installations are made in accordance with the building, electrical, and plumbing codes applicable in the installation region. GENERAL REQUIREMENTS Codes and Regulations Besides these instructions, all installations of the Rheem Crossflow system shall be carried out in accordance with:  Local Regulations ...
  • Page 10 Crossflow and the closest tank, or pipe material other than copper is being used, consult Rheem for appropriate pipe sizing. Connect hot supply from heating source to the fitting marked “Heating Source In” on the Crossflow.
  • Page 11: Potable Water Connections To Crossflow System

    Ensure equal-friction method is used when making the plumbing connections. The potable water flanges may be joined together for up to two Crossflows. Systems greater than this require the potable water to be connected via a common header. Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 12: Electrical Connections

    (Amps) RD200 RD400 220 -240V AC / 50-60Hz RD600 RD800 Wire the power supply to terminals L, N, Earth within the Crossflow system pump controller housing. Crossflow System Wiring Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 13: Water Supplies

    Where the saturation index exceeds +0.40, the water is very scaling and an expansion control valve* must be fitted on the cold water line after the non-return valve for the Rheem warranty to apply to a Rheem storage tank. The Rheem warranty does not apply to the heat exchanger.
  • Page 14 In the table a number of important chemical components are listed, however the actual corrosion is a very complex process influenced by many different components in combination. Rheem's warranty will not cover any resultant faults if the water heater is connected at any time to a water supply that exceeds the limits listed in the table.
  • Page 15: Commissioning Of The Crossflow System

    Home key to return to the home page. Delivery Skid Temperature Settings Model ECO Setting Factory Setting Max Recommended Temp Setting Refer to Grundfos Magna manual supplied with Crossflow for other system options. Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 16: Setting The Globe Valve

    No further adjustments are required to the system. The system is now completely commissioned. Explain operation and hand over to a responsible officer. Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 17: Cleaning The Heat Exchanger

    Ensure pressure limiting valve is of sufficient capacity to meet the requirements of the application.  Is pipe sizing adequate to suit the application?  Check all valves, heat exchangers and pipework for fouling or blockage. Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 18 This page is intentionally blank Copyright Rheem Australia PTY LTD 2016 Dec 2016 AQ0901085 Rev C...
  • Page 19: The Rheem Warranty - General

    (including wind chill factor). If you require a call out and we find that the fault is not covered by the Rheem warranty, you are responsible for our standard call out charge. If you wish to have the relevant component repaired or replaced by Rheem, that service will be at your cost.
  • Page 20 WHAT IS COVERED BY THE RHEEM WARRANTY FOR THE CROSSFLOW IS DETAILED IN THIS DOCUMENT Rheem will repair or replace a faulty component of your Crossflow Delivery Skid if it fails to operate in accordance with its specifications as follows:...