Kako
February 23, 2025

Hello, My generator is showing Sd/ECU. Whenever I want to start the generator the screen goes dark for 1-2 second then shows Sd/ECU and cannot start! any idea of what are the possible solutions?

User image 67baeddfa1a96
1 comments:
Mr. Anderson
May 14, 2025

Possible solutions for a ComAp generator showing Sd/ECU and not starting include:

1. Check RS485 Communication: Ensure the RS485 line is properly connected, not swapped (A and B), and terminated correctly. Avoid long cable runs and reduce electrical interference.

2. Verify Controller Connection: Confirm the controller is properly connected and powered.

3. Update Firmware: If there are errors related to screen templates, fonts, or bitmaps, update the InteliVision 5 firmware and display fonts.

4. Check ECU Inputs and Outputs: Inspect ECU-related binary inputs and outputs such as DEF tank, force regen, and regen inhibit signals.

5. Use Manual Mode: Switch to manual mode using the mode button, then press the green start button.

6. Check for Error Messages: Look for specific error messages like unsupported language or corrupted display elements and correct them by updating or reprogramming as needed.

This answer is automatically generated