10. GENERAL TECHNICAL DATA
Airflow at SFPv
Min. airflow
Size
1.8 (m
/s)
3
011
0.89
012
0.97
014
1.48
020
1.53
025
2.07
030
2.10
035
3.12
040
3.30
050
4.22
060
4.25
070
5.51
080
5.52
1)
For an outdoor temperature of 26°C, 50% RH, extract air temperature of 22°C, supply air temperature 16°C.
Cooling capacity: rotating heat exchange / coil HC.
For an outdoor temperature of -20°C, 95% RH, extract air temperature of 22°C, supply air temperature 20°C.
2)
Heating capacity: rotating heat exchange / coil HC.
Sizing
For correct sizing, we refer to our ProUnit air handling unit
selection program AHU Design.
11. WIRING DIAGRAM
For the wiring diagram, see the separate document.
18
www.swegon.com
Cooling capac-
(m
/s)
ity (kW)
3
1)
0.45
14.8 / 8.2
0.50
15.9 / 8.9
0.75
24.2 / 13.6
0.75
25.0 / 14.1
0.95
33.7 / 19.1
0.95
34.1 / 19.4
1.50
51.2 / 28.5
1.58
53.8 / 30.3
2.05
68.8 / 38.9
2.08
69.3 / 39.2
2.87
90.5 / 50.5
2.92
90.6 / 50.6
Heating capac-
Refrigerant
ity (kW)
(kg)
2)
44.0 / 4.1
6
47.4 / 4.8
8
72.0 / 7.9
8
74.1 / 8.4
10
100.1 / 11.5
10
101.4 / 11.8
13
152.0 / 16.4
18
159.7 / 18.3
20
204.4 / 23.2
17.5
205.7 / 23.5
20
268.8 / 28.7
25
269.2 / 28.8
30
GB.RXHCF.191011
Power supply
3 x 400 V ±10%, +N +PE 16A
3 x 400 V ±10%, +N +PE 25A
3 x 400 V ±10%, +N +PE 25A
3 x 400 V ±10%, +N +PE 25A
3 x 400 V ±10%, +N +PE 25A
3 x 400 V ±10%, +N +PE 32A
3 x 400 V ±10%, +N +PE 50A
3 x 400 V ±10%, +N +PE 50A
3 x 400 V ±10%, +N +PE 63A
3 x 400 V ±10%, +N +PE 63A
3 x 400 V ±10%, +N +PE 63A
3 x 400 V ±10%, +N +PE 80A
We reserve the right to alter specifications.
EER
COP
1)
2)
4.7
3.5
4.6
3.5
5.3
3.6
4.4
3.4
4.4
3.4
4.9
3.4
4.5
3.2
4.9
3.3
4.3
3.1
3.9
3.0
4.0
2.9
4.0
2.9