Danfoss 176F3417 Installation Instructions Manual page 8

Inrush card kit for d1h–d8h drives vlt fc series fc 102, fc 103, fc 202, fc 302

Advertisement

1.4.3 Installing the Inrush Card in D2h/D4h/D7h/D8h Drives
To install the new inrush card, use the following steps. Refer to Illustration 1.5.
1.
Position the inrush card in the drive.
2.
Secure 5 screws (T20) in the inrush card.
3.
Secure 2 thread-forming screws (T20).
4.
Connect the cable to the inrush card connector MK1802.
1.4.4 Reassembling D2h/D4h/D7h/D8h Drives
After installing the new inrush card, replace the following components in the drive. Refer to Illustration 1.4. See the service guide for
detailed instructions for each component.
1.
Replace the power card mounting plate.
2.
Replace the control card mounting plate.