HAZARD SUMMARY

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
mWARNING:
mCAUTION:
CAUTION:
The following safety precautions apply to the instal-
lation, operation, and maintenance of the equipment
described by this technical manual.
mWARNING:
Any unauthorized modification of this equipment
shall void the warranty.
mWARNING:
Only qualified personnel should attempt instal-
lation, service, and repair of this equipment. Use
extreme caution and observe safety regulations at
all times.
mWARNING:
Recirculation of room air is not permitted.
Adequate building relief must be provided so as to not
over pressurize the building when the heating system
is operating at its rated capacity. It should be noted
that this can be accomplished by taking into account,
through standard engineering methods, the structure's
designed infiltration rate, by providing properly sized
relief openings, or by interlocking a powered exhaust
system, or by a combination of these methods.
If the failure or malfunction of this heater creates a
hazard to other fuel burning equipment in the build-
ing, (e.g. when the heater is providing the make-up air
to a boiler room), the unit is to be interlocked to open
inlet air dampers or other such devices.
Cambridge Engineering, Inc.
Indicates a potentially hazardous situation which could result in
death or serious injury.
Indicates a potentially hazardous situation which may result in
minor or moderate injury. It may also be used to alert against
unsafe practices.
Indicates a situation that may result in accidents with equipment or
property damage only.
If the heater is installed such that an inlet duct is
utilized, the duct system must be purged with at least
four air changes prior to an ignition attempt.
Installation in Aircraft Hangars
Refer to the Standard for Aircraft Hangars,
ANSI/NFPA 409, for specific information on the
installation requirements for these heaters in air-
craft hangars.
Installation in Parking Garages
Refer to the Standard for Parking Structures, ANSI/
NFPA 88A, or the Standard for Repair Garages,
ANSI/NFPA 88B, for specific information on the
installation requirements for these heaters in public
garages.
Installation in Car Wash Facilities
A non-recirculating, S-Series Space Heater used in a
Car Wash tunnel application may be designated as a
T-Series Heater on the nameplate.
This S-Series Technical Manual also applies to all
T-Series Heaters.
If in doubt regarding installation application, con-
tact Cambridge Customer Service Group at 1-800-
473-4569 during the hours of 8:00 a.m. to 5:00 p.m.
Central Time, Monday through Friday.
2
IMPORTANT
S-Series Technical Manual