Available Dimensions - Lindab WH45 Series Technical Manual

Circular series
Hide thumbs Also See for WH45 Series:
Table of Contents

Advertisement

WH45
WH45
ovER vIEW
LINDAB SAFE
LINDAB SAFE

Available dimensions

Ø
mm
Performances
Performance
Thermal fuse testing
Open and Close cycle reliability
Resistance to corrosion in humid and saline environments
Casing tightness
Blade seal
(1)
Casing leakage class C for diameter bigger than 315 mm as per EN 1751.
Casing leakage class B minimum for diameter less than or equal to 315 mm as per EN 1751 (class C on request).
Fire resistance classification according to EN 13501-3-2005
EI 120 S Installation within vertical rigid wall  p. 17
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
EI 90 S Installation within vertical rigid wall  p. 17
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Plasterboard and rock wool 100 kg/m³ sealing
ve (i↔o)
EI 90 S Installation within vertical light wall (plasterboard)  p. 19
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ sealing
ve (i↔o)
EI 120 S Installation within vertical light wall (plasterboard)  p. 19
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Mortar or plaster putty sealing
ve (i↔o)
EI 90 S Installation within vertical light wall (gypsum blocks wall)  p. 20
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
EI 120 S Installation within vertical light wall (gypsum blocks wall)  p. 20
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
200
250
300
315
(500 Pa)
W
D
D
W
W
W
355
400
450
500
Reference standard
ISO 10294-4
EN 15650
EN 60068-2-52
EN 1751
EN 1751
EI 180 S
EI 120 S
EI 90 S
(500 Pa)
(500 Pa)
Ø
-
min 200
min 200
max 800
max 800
-
-
min 200
max 800
-
-
min 200
max 800
-
-
min 200
max 800
-
-
min 200
max 800
Ø
-
min 200
min 200
max 800
max 800
560
600
630
710
Class
Compliant
Compliant
Degree of severity 2
Class C (1)
Class 2 minimum
EI 60 S
EI 30 S
(500 Pa)
(500 Pa)
Ø
Ø
Ø
min 200
min 200
max 800
max 800
Ø
Ø
Ø
min 200
min 200
max 800
max 800
Ø
Ø
Ø
min 200
min 200
max 800
max 800
Ø
Ø
Ø
min 200
min 200
max 800
max 800
Ø
Ø
Ø
min 200
min 200
max 800
max 800
Ø
Ø
Ø
min 200
min 200
max 800
max 800
5/36
5/36
800

Advertisement

Table of Contents
loading

This manual is also suitable for:

Circular seriesWh45

Table of Contents