Installations Within Vertical Light Wall (Gypsum Blocks Wall) - Lindab WH45 Series Technical Manual

Circular series
Hide thumbs Also See for WH45 Series:
Table of Contents

Advertisement

WH45
WH45
INSTALLATIoN
LINDAB SAFE
LINDAB SAFE

Installations within vertical light wall (gypsum blocks wall)

Refer to the section Construction supports characteris-
tics  p. 16 for further information.
Comply with the minimum distances indicated on section
Minimum distances  p. 15.
Wall opening
A opening must be provided in the wall as indicated in the
table and in the drawing
EI 90 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum density 995 kg/m³
EI 120 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum density 995 kg/m³
1.
Plaster putty
D
Hole size: see table above
S
Wall minimum thickness: see table above
20/36
20/36
Fire resistance classi-
"D" hole size
fication
[mm]
From Ø + 25
EI 90 S
to Ø+35
(500 Pa)
(square hole)
From Ø + 25
EI 120 S
to Ø+35
(500 Pa)
(circular hole)
Damper positioning
Position the damper in the opening so that the side of the
closing mechanism extends as indicated in the table and
in the drawing.
Filling
Fill the space between the wall and the damper using plas-
ter putty.
Damper protrusion
Wall minimum thick-
from the wall "E"
[mm]
230 + Lp
215 + Lp
E
Damper protrusion from the wall: see table above
Lp
Overlap length between fire damper and duct: see section
Dimension  p. 9
ness "S"
Sealing
[mm]
70
Plaster putty sealing
100
Plaster putty sealing