Victron energy Lynx Ion Manual page 10

24v/180ah lithium ion batteries
Table of Contents

Advertisement

4.5
Connection of the BMS CAN-Bus network
To connect the BMS CAN-Bus communication network you will need:
CAT5 cable with RJ45 connectors
Two termination resistors (supplied with the Lynx Ion)
Procedure
1.
Use connection A of the Lynx Ion, top left pair of RJ45 connectors. Connect the
other end of the CAT5 cable to the first battery.
2.
Then connect it to the second battery (if there is one) with the next CAT5 cable.
3.
Repeat this until all batteries are connected.
4.
Place a termination resistor in the last connected battery.
5.
Place the other termination resistor in the Lynx Ion, connection A.
Now the BMS CAN-Bus network is connected.
4.6
Connection of the VE.Can network
The Lynx Ion is communicating with the Lynx Shunt through VE.Can. This is mandatory.
The VE.Can network is also used to connect the Ion Control.
To connect the Lynx Ion to the Lynx Shunt VE.Can you will need:
One CAT5 cable with RJ45 connectors
Two termination resistors (supplied with the Lynx Shunt VE.Can)
Procedure
1.
Use connection D of the Lynx Ion, the pair of RJ-45 sockets at lower left. Connect
the CAT5 cable to the Lynx Ion, connection D (see Appendix A).
2.
Connect the other end of the CAT5 cable to the Lynx Shunt VE.Can.
3.
Now place the termination resistors. One in the Lynx Ion and one in the Lynx
Shunt.
Now the Lynx Ion and the Lynx Shunt are connected.