Summary of Contents for Leroy-Somer Powerdrive MD2R 100T
Page 1
4948 - 2013.09 / a OPTIONNAL SWITCH SINUS FILTER FA FB FC aR FUSES REGEN INDUCTOR INPUT INPUT FUSES FUSES BOARD BOARD 230V CONTROL INTERFACE BOARD REGEN MD2CI CONTROL BOARD 230V CONTROL MD2CI INTERFACE BOARD MAIN CONTROL BOARD POWERDRIVE MD2R Regenerative variable speed drive Installation and maintenance...
Page 2
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive NOTE leRoY-someR reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. the information contained in this document may therefore be changed without notice. CAUTION For the user's own safety, this variable speed drive must be connected to an approved earth terminal).
Page 3
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES (In accordance with the low voltage directive 2006/95/EC) Throughout the manual, this symbol warns of 5 - Electrical connection consequences which may arise from inappropriate When work is performed on variable speed drives which are use of the drive, since electrical risks may lead to material...
Page 4
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive FOREWORD this manual describes the installation of POWERDRIVE MD2R variable speed drives. It also gives details of all its options and extensions which the user may choose to suit his requirements. POWERDRIVE MD2R Options Parameter setting...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon 1 - GENERAL INFORMATION I(a) = maximum continuous current on mains supply 1.1 - General the nameplate can be found inside the cabinet door at the top (another copy can be found on the outside of the cabinet, at the POWERDRIVE MD2R is a variable speed drive with the top on the right-hand side).
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon 1.4 - Electrical characteristics All work relating to installation, commissioning and maintenance must be carried out by experienced, qualified personnel. 1.4.1 - General characteristics Characteristic Level 3-phase mains supply: 400 V -10% to 480 V +5% ("t"...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon POWERDRIVE MD2R xxxTH Inverter switching frequency = 3 kHz - Active rectifier in factory settings Ambient temperature ≤ 40°C (35°c avec option IP54) - altitude ≤ 1000 m. Heavy duty Normal duty POWERDRIVE...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon 1.4.4 - Derating according to the temperature and switching frequency form motor inverter Ambient temperature ≤ 40°C (≤ 35°C with IP54 option) - altitude ≤ 1000 m Ico (A) Rating Heavy duty...
Page 11
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon Ambient temperature ≤ 50°C (≤ 45°C with IP54 option) - altitude ≤ 1000 m. Ico (A) Rating Heavy duty Normal duty 2 kHz 3 kHz 4 kHz 5 kHz...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon 1.5 - Synoptiques du POWERDRIVE MD2R POWERDRIVE MD2R are composed of : • POWERDRIVE MD2R 180T to 270T • A AFE rectifier • an inverter connected to the motor •...
Page 13
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal InFoRmatIon • POWERDRIVE MD2R 340T to 900T and POWERDRIVE MD2R 270TH to 900TH OPTIONNAL SWITCH 600T / 900T 600TH / 900TH SINUS SINUS FILTER FILTER (FPB) (FO)
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive mecHanIcal InstallatIon 2 - MECHANICAL INSTALLATION l = 400 mm or 600 mm or 600 + 400 mm • It is the responsibility of the owner or user of the POWERDRIVE MD2R to ensure that the installation, 60°...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive mecHanIcal InstallatIon 2.3 - Installation recommendations 2.5 - Assembly and dismantling of the IP54 roof The drives must be installed away from conducting dust, corrosive gas, dripping water and any source of •...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive mecHanIcal InstallatIon 2.6 - Dimensions the cabinet-mounted POWERDRIVE MD2R solution is obtained by assembling cabinet modules 600 mm wide and 600 mm deep. the table below gives the product width (W in mm) depending on the options incorporated: W/o options (-B) With options (-O) Width...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive mecHanIcal InstallatIon 2.7 - Weight 2.8.1 - Drive ventilation flow rates and noise levels the values indicated in the table below are maximum net weights. Forced Noise level ventilation...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3 - CONNECTIONS • All connection work must be performed by • The voltages on the connections of the mains supply, qualified electricians in accordance with the laws in the motor, the braking resistor or the filter may cause force in the country in which the drive is installed.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.1.2 - Electronics and forced ventilation power supply • Disconnection of forced ventilation units the control electronics and forced ventilation units are supplied through a single-phase transformer which primary the fuse board described in section 3.1.1.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.1.4 - Location of power terminal blocks and fuse boards Inverter control board (motor) with control terminal block Synchronous rectifier control board Fuse board and external power supply (included in the chassis oh the product from 60t to 270t) Rating 180T to 270T Rating 60T to 150T P1 P2...
Page 21
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons Rating 340T to 470T and 270TH to 500TH P1 P2 P1 P2 4 x d =11 50 75 Front side of the power terminal block right side...
Page 22
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons Rating 600T to 900T and 600TH to 900TH P1 P2 P1 P2 P1 P2 P1 P2 50 75 Front side of the power terminal block 4 x d =11 Right side...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.1.4 - Cables and fuses • It is the responsibility of the user to connect and provide protection for the POWERDRIVE MD2R in accordance with the current legislation and regulations in the country of use.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.2 - Connection of the control AI1+ differential analog input 1 (+) AI1- differential analog input 1 (-) • The POWERDRIVE MD2R inputs have a positive logic configuration.
Page 25
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons analog output digital output Factory setting 4-20 ma motor current signal Factory setting Zero speed Bipolar analog voltage in common characteristic open collector output type mode or unipolar current in absolute maximum voltage + 30 V/0 V...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.2.3 - Factory configuration of control this setting is obtain from a drive in " factory setting " (default parameter) and modifications as mentionned below. terminal blocks Nota : For more details on the parameters, please refer to the POWERDRIVE MD2R include two modules control :...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive connectIons 3.3 - STO-1/STO-2 inputs: Safe Torque 3.3.1 - Single channel locking (SIL1 - PLb) Off function 3-phase ac power supply, in accordance with safety standard Iec/en 62061: 2005 and en/Iso 13849-1: 2006 - single the sto-1 and sto-2 inputs are safety inputs that can be channel locking (sIl1 - Plb).
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal emc - HaRmonIcs - maIns InteRFeRence 4 - GENERAL EMC - HARMONICS - 4.3 - Radio-frequency interference: Emission MAINS INTERFERENCE 4.3.1 - General the power structure of frequency inverters leads to the occurrence of two types of phenomenom : In order to limit motor losses and obtain a low level of - low-frequency harmonics fed back to the mains supply...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal emc - HaRmonIcs - maIns InteRFeRence 4.4.2 - Mains transient overvoltages 4.4.4 - Ground connections there are numerous sources of overvoltages on an electrical the equipotential earth bonding of some industrial sites installation: is not always observed.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal emc - HaRmonIcs - maIns InteRFeRence 4.5 - Basic precautions for installation these should be taken into account when wiring the cabinet a separate Pe protective conductor is mandatory if the and the external components.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive GeneRal emc - HaRmonIcs - maIns InteRFeRence 4.6 - Electromagnetic compatibility (EMC) CAUTION: Conformity of the drive is only assured when the mechanical and electrical installation instructions described in this manual are adhered to.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons • Architecture 5.1.2 - MDX-SOFT the mdX-soFt enables parameter setting or supervision of From the welcome screen, press the button to access the the POWERDRIVE MD2R from a Pc.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons 5.2 - Add-on options 5.2.2 - Speed feedback option 5.2.2.1 - MDX-ENCODER the control board of the POWERDRIVE MD2R' motor inverter; is designed to be plugged with various optional the mdX-encodeR option is used to manage the motor modules.
Page 35
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons • Connection of an incremental encoder • Connection incremental encoder with commutation channels MDX-ENCODER wiring MDX-ENCODER wiring encoder power supply 0 V encoder power supply 0 V 5 V or 15 V power supply depending on encoder characteristics.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons 5.2.3 - MDX-I/O TIMER option 5.2.2.2 - MDX-RESOLVER • General: the mdX-ResolVeR option is used to manage the motor speed feedback. It manages 2 to 8 poles resolvers. the mdX-I/o tImeR option is used to: •...
Page 37
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons 5.2.4.2 - MDX-Speed feedback or MDX-Fieldbus option 5.2.4.3 - MDX-Speed feedback option combined with a note: In the case of the use of one of these modules with CM-Fieldbus module mdX-I / o tImeR module refer directly to §.5.2.4.4 note: In the case of the use of one of these modules with...
Page 38
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons 5.2.4.4 - MDX-I/O TIMER option the mdX-I/o timer option is installed on the control board of the POWERDRIVE MD2R' motor inverter; if a mdX-speed feedback and/or mdX-Fieldbus option needs to be added, it should be installed on the mdX-I/o tImeR option.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive PaRameteR-settInG InteRFace and oPtIons 5.3 - Electrical protections 5.3.2 - Fuse combination switch the POWERDRIVE MD2R can be installed In the factory, a switching device can be integrated as an with a 3 poles gG fuses combination switch option to the POWERDRIVE MD2R.
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive tRIPs - dIaGnostIcs 6 - TRIPS - DIAGNOSTICS 6.3 - Tripping on a safetrip If the drive trips, the drive output bridge is inactive, and the 6.1 - Safety notice drive no longer controls the motor.
Page 41
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive tRIPs - dIaGnostIcs Parameter- setting interface Reason for trip Solution name • check the braking resistor wiring and insulation level. Braking IGBt transistor overcurrent • make sure that the resistor ohmic value is compatible with Brak.
Page 42
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive tRIPs - dIaGnostIcs Parameter- setting interface Reason for trip Solution name opening of the Ptc input of the PX1 • check the ambient temperature around the motor. terminal block or t1 and t2 inputs of the •...
Page 43
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive tRIPs - dIaGnostIcs Parameter- setting interface Reason for trip Solution name the do2 output load current (mdX-I/o DO2 MDX-I/O check that do2 is not short-circuited. TIMER over ld tImeR option) is >200 ma the do3 output load current (mdX-I/o...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive maIntenance 7 - MAINTENANCE • Preventive maintenance • All work relating to installation, commissioning maintenance must carried experienced, qualified personnel. Device Action Frequency • When a trip detected by the drive causes the motor to clean 3 months stop, fatal residual voltages remain on the terminals and...
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive maIntenance 7.4 - Location of the POWERDRIVE MD2R components, integrated in the POWERDRIVE cabinet : • Ratings 340T to 470T and 270TH to 500TH (1 MD2CI rectifier et 1 MD2CI inverter module) Ratings 600T to 900T and 600TH to 900TH (2 MD2CI Ratings 60T à...
Page 47
LEROY-SOMER InstallatIon and maIntenance 4948 - 2013.09 / a POWERDRIVE MD2R Regenerative variable speed drive maIntenance • Sinus filter and active rectifier protection fuses (see § 1.5) : Sinus filter fuses Active rectifier fuses Ratings FH x3 FO x3 FP x3 FA, FB, FC FQ, FR, FS FPB x3...
Page 48
ImP 297 no 640 Moteurs Leroy-Somer Headquarter: Boulevard Marcellin Leroy - CS 10015 16915 ANGOULÊME Cedex 9 Limited company with capital of 65,800,512 € RCS Angoulême 338 567 258 www.leroy-somer.com...
Need help?
Do you have a question about the Powerdrive MD2R 100T and is the answer not in the manual?
Questions and answers