Motor cooling 2. General description Outdoor installation Drain holes Grundfos MGE 71, MGE 80, MGE 90, MGE 100, MGE 112 and Cable entries MGE 132 are fan-cooled, asynchronous, squirrel-cage motors Terminal box position designed according to current IEC, DIN and VDE guidelines and Electrical connection - single-phase motors standards.
Electronic control condensed water. Frame size (centre line height of MGE 71 and MGE 80 motor shaft in mm, foot-mounted The motor has a plugged drain hole on the drive side. The flange motor) can be turned 90 °...
5 minutes. MGE 71 and MGE 80 5.1 Mains switch The motor must be connected to an external all-pole mains switch with a contact separation of at least 3 mm in each pole according ELCB to IEC 364.
EN 61800-5-1. regulations. Protective earth conductors must always have a yellow/green MGE 71 and MGE 80 (PE) or yellow/green/blue (PEN) colour marking. As the leakage current of 4 kW to 7.5 kW motors is > Caution 3.5 mA, these motors must be connected to...
6.3 Additional protection 6.7 Supply voltage 3 x 380-480 V - 10 %/+ 10 %, 50/60 Hz, PE. If the motor is connected to an electric installation where an earth • leakage circuit breaker is used as additional protection, this The supply voltage and frequency are marked on the motor circuit breaker must be of the type: nameplate.
6.9 Other connections 7. Signal cables The connection terminals of external potential-free contacts for • Use screened cables having a cross-sectional area of min. start/stop, external setpoint signal and relay signal are shown in 0.5 mm and max. 1.5 mm for external on/off switch and fig.
9. Indicator lights and signal relay Green The operating condition of the motor is indicated by the green and red indicator lights in the motor terminal box. See figs and 15. Green Signal relay Fig. 15 Indicator lights and signal relay in three-phase motors Signal relay Fig.
10. Megging 12. Technical data - three-phase motors 12.1 Supply voltage Megging of an installation incorporating MGE motors is not allowed, as the built-in electronics may be Note 3 x 380-480 V - 10 %/+ 10 %, 50/60 Hz, PE. •...
EN 61800-3. 1. Use the public or private waste collection service. Residential areas - unlimited distribution, corresponding to 2. If this is not possible, contact the nearest Grundfos company CISPR 11, class B, group 1. or service workshop. Industrial areas - unlimited distribution, corresponding to CISPR 11, class A, group 1.