Control Inputs/Outputs; Table 18 - I/O Digital Inputs; Table 19 - I/O Digital Outputs; Table 20 - I/O Analog Inputs - York YCWL0056SE Installation Operation & Maintenance

Water-cooled liquid chillers
Table of Contents

Advertisement

FORM 201.26-NM1
ISSUE DATE: 1/19/2018
The digital inputs will display the input connection and
ON/OFF status such as:
F L O W
S W / R E M
J 13 - 5
This indicates that the flow switch/remote start input is
connected to plug 13- pin 5 (J13-5) on the microboard,
and is ON (ON = +30VDC unregulated input, OFF =
0VDC input on digital inputs).

CONTROL INPUTS/OUTPUTS

These tables are a quick reference list providing the
connection points and a description of the inputs and
outputs respectively. All input and output connections
pertain to the connections at the microboard.

TABLE 18 - I/O DIGITAL INPUTS

J13-2
Unit ON/OFF Switch
J13-3
Load Limit Stage 2 on 3, 5 and 6 Comp. Units
J13-4
Load Limit Stage 1
J13-5
Flow Switch and Remote Start/Stop
J13-6
Spare
Single System Select
J13-7
(Jumper = Single Sys, No Jumper = Two Sys)
CR1
J13-8
(Sys 1 Motor Protector/High Pressure Cutout)
CR2
J13-10
(Sys 2 Motor Protector/High Pressure Cutout)
JOHNSON CONTROLS
S T A R T
I S
O N
SECTION 9 – SERVICE AND TROUBLESHOOTING

TABLE 19 - I/O DIGITAL OUTPUTS

TB7-2
SYS 1 Compressor 1
TB7-3
SYS 1 Liquid Line Solenoid Valve
TB7-4
SYS 1 Compressor 2
TB7-5
SYS 1 Compressor 3
TB7-7
SYS 1 Hot Gas Bypass Valve
TB10-2
SYS 2 Compressor 1
TB10-3
SYS 2 Liquid Line Solenoid Valve
TB10-4
SYS 2 Compressor 2
TB10-5
SYS 2 Compressor 3
TB7-8
SYS 1 Condenser Fan Output 1 (N/A)
TB7-9
SYS 1 Condenser Fan Output 2 (N/A)
TB7-10
SYS 1 Condenser Fan Output 3 (N/A)
TB10-8
SYS 2 Condenser Fan Output 1 (N/A)
TB10-9
SYS 2 Condenser Fan Output 2 (N/A)
TB10-10
SYS 2 Condenser Fan Output 3 (N/A)
TB8-2
Evaporator Heater
TB8-3
SYS 1 Alarm
TB9-2
SYS 2 Alarm
TB8-6 & 7 Evaporator Pump Starter
TB10-7
SYS 2 Hot Gas Bypass Valve

TABLE 20 - I/O ANALOG INPUTS

SYS 1 Suction Transducer
J7-10
-or-
SYS 1 Low Pressure Switch
Unit Type: Chiller = NO Jumper J11-12 to +24
VDC
J11-12
YCUL Condensing Unit = Jumper J11-12 to +24
VDC (Do NOT Use)
SYS 1 Discharge Pressure Transducer
J7-11
(Standard)
J6-9
Ambient Air Temp. Sensor
J6-7
Leaving Chilled Liquid Temp. Sensor
J6-8
Return Chilled Liquid Temp. Sensor
SYS 2 Suction Pressure Transducer
J9-10
-or-
SYS 2 Low Pressure Switch
SYS 2 Discharge Pressure Transducer
J9-11
(Standard)
J7-12
Unit/SYS 1 Voltage
J9-12
SYS 2 Voltage
J11-11 Remote Temperature Reset

TABLE 21 - I/O ANALOG OUTPUTS

N/A
Not Applicable
9